| 2022-04-04 14:35:33 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22030512 | | | | | | CODES IN EFFECT: | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE ADD A NOTE ON THE MECHANICAL DRAWINGS STATING | | | THAT THE REFRIGERATION WILL REQUIRE A SEPARATE PERMIT | | | AND REVIEW AS THE WALK-INS WILL NOT BE REVIEWED UNDER | | | THIS PERMIT. | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FEC C403.2.1 | | | | | | 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS | | | ACCORDING TO FMC 403.3.1.1 3RD SENTENCE WE MUST USE | | | TABLE 403.3.1.1 AND NOT THE ARCHITECT?S EGRESS | | | OCCUPANCY COUNT. PLEASE DO NOT FORGET THE EXHAUST FOR | | | THIS KITCHEN. FMC 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | 4) PLEASE SHOW THE LOCATION OF THE CONDENSING UNIT AND | | | THE ANCHORAGE OF THIS UNIT. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|