Plan Review Notes
Plan Review Notes For Permit 22030512
Permit Number 22030512
Review Stop M
Sequence Number 1
Notes
Date Text
2022-04-04 14:35:331ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22030512
  
 CODES IN EFFECT:
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE ON THE MECHANICAL DRAWINGS STATING
 THAT THE REFRIGERATION WILL REQUIRE A SEPARATE PERMIT
 AND REVIEW AS THE WALK-INS WILL NOT BE REVIEWED UNDER
 THIS PERMIT.
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FEC C403.2.1
  
 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS
 ACCORDING TO FMC 403.3.1.1 3RD SENTENCE WE MUST USE
 TABLE 403.3.1.1 AND NOT THE ARCHITECT?S EGRESS
 OCCUPANCY COUNT. PLEASE DO NOT FORGET THE EXHAUST FOR
 THIS KITCHEN. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 4) PLEASE SHOW THE LOCATION OF THE CONDENSING UNIT AND
 THE ANCHORAGE OF THIS UNIT. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  