| 2022-06-10 13:16:39 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY |
| | CALCULATIONS TO CORRECT DESIGN PRESSURES & NAILING |
| | PATTERNS. PROVIDE CORRECT DESIGN PRESSURES AND NAILING |
| | PATTERNS FOR ZONE #1 PRIME, ZONE #1, ZONE #2 & ZONE #3 |
| | AS PER SECTION R301 OF THE 2020 FBC R. EXAMPLE: |
| | EXPOSURE CATEGORY D ZONE 3 MINIMUM DESIGN PRESSURE |
| | REQUIREMENT IS -141.0. |
| | 2. FBC B 107.1 IF THE DESIGN PROFESSIONAL IS AN |
| | ARCHITECT, INTERIOR DESIGNER, OR ENGINEER LEGALLY |
| | REGISTERED UNDER THE LAWS OF THE STATE OF FLORIDA |
| | REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR |
| | DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA |
| | STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED |
| | FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR |
| | ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA |
| | STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE. |
| | ENHANCED ENGINEER NAILING CALCS HAS NO SEAL AFFIXED. |
| | 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R33 |
| | HAS BEEN REVISED TO FL5259-R35. PLEASE PROVIDE A |
| | COMPLETE SET. |
| | 4. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R33 |
| | (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF |
| | WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT |
| | CONSIDER USING FL5259-R35 (NON-HVHZ). |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |