| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. FBC B 107.1 IF THE DESIGN PROFESSIONAL IS AN |
| | ARCHITECT, INTERIOR DESIGNER, OR ENGINEER LEGALLY |
| | REGISTERED UNDER THE LAWS OF THE STATE OF FLORIDA |
| | REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR |
| | DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA |
| | STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED |
| | FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR |
| | ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA |
| | STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE. |
| | 2. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY |
| | CALCULATIONS TO CORRECT EXPOSURE CATEGORY, DESIGN |
| | PRESSURES & NAILING PATTERNS. PROVIDE CORRECT DESIGN |
| | PRESSURES AND NAILING PATTERNS FOR ZONE #1 PRIME, ZONE |
| | #1, ZONE #2 & ZONE #3 AS PER SECTION R301 OF THE 2020 |
| | FBC R. THE CORRECT EXPOSURE FOR THE PROJECT LOCATED AT |
| | 6701 PAMELA LN WEST PALM BEACH IS EXPOSURE CATEGORY D. |
| | 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED ROOF SKYLIGHT SYSTEM |
| | TO BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. SECOND |
| | REQUEST. |
| | 4. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED ROOF RIDGE VENT SYSTEM |
| | TO BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. SECOND |
| | REQUEST. |
| | 5. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R34 |
| | HAS BEEN REVISED TO FL5259-R35. PLEASE PROVIDE A |
| | COMPLETE SET; IT COVERS MULTIPLE PRODUCT TYPES; ROOF |
| | COVER OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE |
| | COMBINATIONS, ALLOWABLE SUBSTRATES & ATTACHMENT |
| | LIMITATIONS. SELECT OPTIONS FROM EACH CATEGORY TO BE |
| | USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE |
| | CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN |
| | PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | SECOND REQUEST. |
| | 6. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S). FLAT/LOW |
| | SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. SECOND |
| | REQUEST. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |