| 2022-03-25 08:27:28 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-22030450 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) AN ENERGY CALCULATION MUST BE SUBMITTED FOR EACH |
| | TOWN HOUSE, THIS SUBMITTAL MUST INCLUDE THE ADDRESS FOR |
| | EACH TOWNHOME. FBC EC R402 |
| | |
| | 2) A MECHANICAL EQUIPMENT SIZING CALCULATION MUST BE |
| | SUBMITTED FOR EACH TOWN HOUSE. FBC EC R403.7 |
| | |
| | 3) THE PERMIT APPLICATION MUST HAVE THE CORRECT ADDRESS |
| | FOR EACH TOWN HOUSE. FBC 107.2.1 |
| | |
| | 4) EACH TOWN HOUSE MUST HAVE A SEPARATE PERMIT |
| | APPLICATION. THE PERMIT APPLICATIONS ?WORK DESCRIPTION? |
| | STATES NEW CONSTRUCTION OF 7 TOWNHOUSES ON EACH |
| | APPLICATION SUBMITTED. PLEASE SHOW THAT EACH |
| | APPLICATION IS FOR A SPECIFIC ADDRESS AND PROJECT FOR |
| | THAT ADDRESS. FBC 107.2.1 |
| | |
| | 5) UNIT SHEETS: KEYNOTE 3 SPECS OUT A RE-CIRCULATING |
| | TYPE RANGE HOOD BUT IN THE SUPPORTING DOCUMENTS THERE |
| | IS A 600 CFM HOOD EXHAUST FAN. PLEASE EITHER SHOW THE |
| | DUCTWORK FOR THE HOOD AND THE TERMINATION LOCATION OR |
| | REMOVE THE 600 CFM HOOD MOTOR IN THE SUPPORTING |
| | DOCUMENTS FOR THIS SUBMITTAL. FBC 107.2.1 |
| | |
| | 6) PLEASE PROVIDE VENTILATION REQUIREMENTS FROM THE |
| | MANUFACTURER FOR THE POOL MOTOR AND POOL PUMPS THAT ARE |
| | LOCATED IN THE GARAGES. FBC 107.2.1 |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |