| 2022-03-25 10:49:55 | 03/25/22 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. PLEASE PLACE A NOT ON PLANS. |
| | |
| | 2. WOULD YOU PLEASE SUBMIT EACH LENGTH OF ALL CUT |
| | SECTIONS OF PIPE ON THE ISOMETRIC DRAWING PER 2020 FBC |
| | RES. SECS. G2413.4.1, G2413.4.2. |
| | |
| | 3. IS THE POOL HEATER IN A GARAGE? WOULD YOU PLEASE |
| | SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE FBC RES. |
| | SEC. G2407.1 AND G2439.4. IF THE LOUVER IS USED, SHOW |
| | THE LOUVERS' LOCATIONS THAT ARE BEING INSTALLED FOR THE |
| | COMBUSTION AIR. THE LOUVERS CANNOT BE LOCATED ON AN |
| | EXTERIOR WALL THAT IS FIRE RATED AS THE FIRE RATING OF |
| | THE WALL MUST BE MAINTAINED PER THE WPB AMENDMENTS TO |
| | FBC SEC.107.2.1. PLEASE PROVIDE VENTING DIAGRAMS |
| | SHOWING THE TYPE AND SIZE OF GAS VENTS, GAS VENT RUNS, |
| | AND TERMINATION LOCATIONS FOR POOL HEATER PER THE 2020 |
| | FBC FG SEC. 503. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF THE DELIVERY GAS |
| | METER TO THE MOST REMOTE OUTLET IN THE BUILDING AND/OR |
| | SYSTEM PER THE 2020 FBC RES. SEC. G2413.4.1. |
| | |
| | 5. LIST THE BTU LOAD OF EACH APPLIANCE WITH THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. |
| | G2413. |
| | |
| | 6. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR |
| | NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7. INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) ON THE |
| | PLAN PER THE 2020 FBC RES. SEC. G2413.2. |
| | |
| | 8. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS |
| | FOR ALL EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC |
| | RES. SEC. G2408.1. GAS APPLIANCES SHALL BE LISTED AND |
| | LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION PER THE 2020 FBC RES. SEC. G2413.2 AND |
| | G2404.3. |
| | |
| | 9. A GAS GRILL IS LABELED FOR OUTDOOR USE, AND IT SEEMS |
| | TO BE IN A COVERED PATIO; IF SO, PLEASE PROVIDE |
| | MANUFACTURERS RECOMMENDATION FOR A VENTILATION HOOD PER |
| | THE 2020 FG 305.1 OR 2020 FBC RES. SEC. G2408.1. A |
| | SEPARATE PERMIT MAY BE REQUIRED FOR HOOD PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 10. WOULD YOU PLEASE LABEL THE SHUTOFF VALVES AND DRIP |
| | LEGS ON GAS ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5 |
| | AND SHOW SHUT OFF ON THE MAIN METER, PLEASE. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |