| 2022-04-12 17:02:01 | NEW TOWNHOUSE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE SHOW THE EMERGENCY EGRESS FROM THE 2ND FLOOR |
| | BEDROOMS THAT LEAD DIRECTLY TO A PUBLIC WAY - FBC |
| | R310.1 EMERGENCY ESCAPE AND RESCUE OPENING REQUIRED. |
| | BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM |
| | SHALL HAVE NOT LESS THAN ONE OPERABLE EMERGENCY ESCAPE |
| | AND RESCUE OPENING. WHERE BASEMENTS CONTAIN ONE OR MORE |
| | SLEEPING ROOMS, AN EMERGENCY ESCAPE AND RESCUE OPENING |
| | SHALL BE REQUIRED IN EACH SLEEPING ROOM. EMERGENCY |
| | ESCAPE AND RESCUE OPENINGS SHALL OPEN DIRECTLY INTO A |
| | PUBLIC WAY, OR TO A YARD OR COURT THAT OPENS TO A |
| | PUBLIC WAY. |
| | |
| | 2) PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE OVERHEAD |
| | GARAGE DOOR - THE GARAGE DOOR PRODUCT APPROVAL SHOWN ON |
| | THE DRAWINGS ALLOWS FOR BOTTOM VENTS OF 120 SQUARE |
| | INCHES MAX. - CUTTING HOLES IN THE GARAGE DOOR FOR |
| | FLOOD VENTS WILL VOID THE PRODUCT APPROVAL - PLEASE |
| | PROVIDE DETAILS FROM A DESIGN PROFESSIONAL TO INSTALL |
| | FLOOD VENTS IN THE OVERHEAD GARAGE DOOR BEYOND THE 120 |
| | SQUARE INCHES ALLOWED BY THE PRODUCT APPROVAL. |
| | |
| | 3) FLOOD VENTS SHOULD BE PLACED IN OPPOSITE SIDES OF |
| | THE BUILDING - PLEASE SHOW FLOOD VENTS IN THE SIDE OF |
| | THE BUILDING WHERE POSSIBLE FBC R322.2.2.1 |
| | |
| | 4) PLEASE SHOW THE REQUIRED WIND DESIGN PRESSURE FOR |
| | THE WINDOW AND DOOR OPENINGS FBC R301.2.1 |
| | |
| | 5) PLEASE PROVIDE THE ADDITIONAL ROOF SYSTEM ATTACHMENT |
| | DETAILS FROM A DESIGN PROFESSIONAL FOR WIND ZONES 2 AND |
| | 3 AS NOTED ON THE ROOF SYSTEM PRODUCT APPROVAL. |
| | |
| | 6) PLEASE SHOW THE "PLUNGE POOL" BARRIER FROM THE |
| | RESIDENCE PER FBC R4502.17.1 |
| | |
| | 7) PLEASE PROVIDE AN ELEVATION CERTIFICATE MARKED |
| | "CONSTRUCTION DRAWINGS" FBC WPB 107.3.5.3 |
| | |
| | 8) PLEASE SHOW EQUIPMENT ELEVATION IN THE GARAGE OR |
| | OUTSIDE THE BUILDING FBC R322.1.6 PROTECTION OF |
| | MECHANICAL, PLUMBING AND ELECTRICAL SYSTEMS. |
| | ELECTRICAL SYSTEMS, EQUIPMENT AND COMPONENTS; HEATING, |
| | VENTILATING, AIR CONDITIONING; PLUMBING APPLIANCES AND |
| | PLUMBING FIXTURES; DUCT SYSTEMS; AND OTHER SERVICE |
| | EQUIPMENT SHALL BE LOCATED AT OR ABOVE THE ELEVATION |
| | REQUIRED IN SECTION R322.2 OR R322.3. |
| | |
| | 9) THE WALLS SEPARATING THE TOWNHOUSES CANNOT HAVE |
| | OPENINGS BELOW THE 2ND FLOOR IN THE COURT YARD AREA - |
| | FBC R302.2.1 CONTINUITY. |
| | THE FIRE-RESISTANCE-RATED WALL OR ASSEMBLY SEPARATING |
| | TOWNHOUSES SHALL BE CONTINUOUS FROM THE FOUNDATION TO |
| | THE UNDERSIDE OF THE ROOF SHEATHING, DECK OR SLAB. THE |
| | FIRE-RESISTANCE RATING SHALL EXTEND THE FULL LENGTH OF |
| | THE WALL OR ASSEMBLY, INCLUDING WALL EXTENSIONS THROUGH |
| | AND SEPARATING ATTACHED ENCLOSED ACCESSORY STRUCTURES. |
| | |
| | 10) DRAWING S2 SHOWS A CUT SECTION (9/S6) AND (10/S6) |
| | WHICH SHOWS THE FLOOR SHEATHING RUNNING CONTINOUS |
| | THROUGH THE COMMON 2 HR RATED WALL FBC R302.2.1 |
| | CONTINUITY. |
| | THE FIRE-RESISTANCE-RATED WALL OR ASSEMBLY SEPARATING |
| | TOWNHOUSES SHALL BE CONTINUOUS FROM THE FOUNDATION TO |
| | THE UNDERSIDE OF THE ROOF SHEATHING, DECK OR SLAB. THE |
| | FIRE-RESISTANCE RATING SHALL EXTEND THE FULL LENGTH OF |
| | THE WALL OR ASSEMBLY, INCLUDING WALL EXTENSIONS THROUGH |
| | AND SEPARATING ATTACHED ENCLOSED ACCESSORY STRUCTURES. |
| | |
| | 11) A SEPARATE PERMIT IS REQUIRED FOR - SITE LIGHTING, |
| | FENCING, POOL. |
| | |