| 2022-04-07 11:41:14 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET FP 24 ROOF B - THERE IS AN INDICATION OF A |
| | HOSE VALVE CONNECTION THAT APPEARS TO BE OBSTRUCTED BY |
| | A BOXED WALL AREA. |
| | |
| | PER NFPA 14 |
| | |
| | 7.3 LOCATIONS OF HOSE CONNECTIONS. |
| | 7.3.1* GENERAL. |
| | 7.3.1.1 HOSE CONNECTIONS AND HOSE STATIONS SHALL BE |
| | UNOBSTRUCTED AND SHALL BE LOCATED NOT LESS THAN 3 FT |
| | (0.9 M) OR MORE |
| | THAN 5 FT (1.5 M) ABOVE THE FLOOR |
| | |
| | THE HVC NEEDS TO BE RELOCATED AT LEAST TO THE OTHER |
| | CORNER OF THE BOXED AREA OR OUT IN FRONT OF THE BOXED |
| | WALL AREA SO THAT IT IS MORE VISIBLE AND ACCESSIBLE TO |
| | FD OPERATIONS. |
| | |
| | ADDITIONALLY, A FD HOSE CONNECTION SIGN WILL BE |
| | REQUIRED SO THAT IT CAN BE SEEN FROM ABOVE THE AREA A/C |
| | EQUIPMENT. |
| | |
| | PLEASE CORRECT AND PROVIDE A NOTE FOR THE SIGN ON THE |
| | PLAN SHEET. |
| | |
| | |
| | 2) ANY FIRE LINE UNDERGROUND RELATED TO THIS PERMIT'S |
| | PROPOSED WORK SHALL BE DONE UNDER SEPARATE PERMIT AND |
| | SHOP DRAWINGS. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A NOTE |
| | OF ACKNOWLDGMENT ON SHEET FP 3. |
| | |
| | |
| | |
| | |
| | 3) SHEET FP 1 - WITHIN THE FIRE SPRINKLER HEAD LEGEND |
| | THERE ARE NO INDICATIONS OF THE TOTAL NUMBER OF EACH |
| | HEAD TYPE. |
| | |
| | THE TOTAL OF THOSE HEADS SHOULD MATCH THE TOTAL FOR THE |
| | JOB. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 4) SHEET FP 4 L01A - PLEASE REVIEW THE TOTALS FOR THE |
| | TOTAL THIS SHEET FOR HEADS TY-FRB HSW (5) , TY-FRB HSW |
| | (3) AS THESE NUMBERS CANNOT BE VERIFIED WITHIN THE |
| | FLOOR PLAN. |
| | |
| | ADDITIONALLY, PLEASE REVIEW THE SIMILAR LEGENDS ON |
| | OTHER SHEETS FOR THESE HEADS AS THEY ALSO CANNOT BE |
| | VERIFIED. |
| | |
| | |
| | |
| | 5) SHEET FP 25 - IT COULD NOT BE EASILY IDENTIFIED DUE |
| | TO THE PLAN SHEET WITH COLORS COMES OUT VERY BLURRY, |
| | BUT ARE THERE INDICATION OF PRV'S WHERE REQUIRED ON THE |
| | APPLICABLE FLOORS AND FD HOSE CONNECTIONS? |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE ON THE PLAN SHEET |
| | EITHER IT WILL BE PROVIDED OR THAT IT WILL NOT WITH |
| | DETAILS. |
| | |
| | |
| | 5A) SHEET FP 25 - THERE IS NO INDICATION OF THE ROOF |
| | FDHC THAT IS INDICATED ON SHEET FP 24 ROOF B. |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE A NOTE OF |
| | EXPLANATION/CLARIFICATION. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |