Plan Review Notes
Plan Review Notes For Permit 22030386
Permit Number 22030386
Review Stop M
Sequence Number 1
Notes
Date Text
2022-03-17 11:51:221ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22030386
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL INSTALLATION FOR THIS PROJECT WILL
 REQUIRE A MECHANICAL SUB-PERMIT.
  
 2) PLEASE SHOW THE RATED WALLS AT THE AHU-1 AS IT IS
 UNCLEAR TO THIS REVIEWER HOW THE RETURN AIR WILL BE
 ABLE TO RETURN BACK TO THE AHU-1 FROM THE CONDO. FBC
 107.2.1
  
 3) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 4) PLEASE SHOW WHERE THE CONDENSING UNIT WILL BE
 LOCATED FOR THIS MECHANICAL SYSTEM. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  