| Plan Review Notes For Permit 22030386 |
| Permit Number |
22030386 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-09 12:46:29 | FIRE REVIEW COMMENTS: | | | FOR CLARIFICATION OF THE PLAN SUBMITTED, THE TITLE | | | SHEET NOTE 38 STATES THE CONTRACTOR SHALL MAINTAIN ALL | | | LIFE SAFETY SYSTEMS IN OPERATION. THE DEMO SHEET HAS | | | SEVERAL LOCATIONS WHERE THE CONTRACTOR IS TO REMOVE AND | | | CAP FIRE SPRINKLER HEADS AS NEEDED. PLEASE ADDRESS HOW | | | ADEQUATE FIRE SPRINKLER COVERAGE WILL BE MAINTAINED. | | | ANY WORK PERFORMED CONNECTED TO THE BUILDING FIRE ALARM | | | SYSTEM WILL REQUIRE A SEPARATE PERMIT AND SHOP DRAWINGS | | | TO BE SUBMITTED AND APPROVED. | | | REVIEW PERFORMED BY, | | | RANDY WALKER, SENIOR FIRE INSPECTOR | | | (561) 804-4762 | | | [email protected] | | | |
|