| Plan Review Notes For Permit 22030382 |
| Permit Number |
22030382 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-09-06 13:13:10 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PRODUCT APPROVAL PROVIDED FOR THE ROOFING NEEDS TO | | | BE REVIEWED AND MARKED APPROVED BY THE BUILDING | | | DESIGNER OF RECORD - FBC WPB 107.3.4 | | | | | | 2) SOME DRAWINGS SHOW A TILE ROOF AT FRONT ENTRY - SOME | | | DRAWINGS SHOW A FLAT ROOF AT FRONT ENTRY - PLEASE | | | CLARIFY - ALL DRAWINGS SHOULD MATCH. | | | | | | 3) AC CALCULATIONS PROVIDED SHOW R30 INSULATION IN THE | | | CEILING - PLEASE SHOW THE TYPE OF INSULATION ON THE | | | DRAWINGS. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|