Plan Review Notes
Plan Review Notes For Permit 22030377
Permit Number 22030377
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-06-24 10:53:39THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L.
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 THE DOOR SCHEDULE DOESN'T SHOW THE FIRE RATING FOR THE
 FIRE DOOR AND ITS ASSEMBLY. THE DOOR THATS BEING
 REPLACED IS REQUIRED TO HAVE A RATING MATCHING THE
 RATING IN NFPA 101 TABLE 8.3.4.2
  
 ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL REMAIN
 ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION PERIODS.
  
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561-804-4728
 [email protected]