| 2022-04-06 14:26:09 | 1ST REVIEW FMC |
| | PERMIT: 22030340 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE PERMIT APPLICATION SHOULD REFLECT THE FLOOR |
| | NUMBERS OF THIS PROJECT. |
| | |
| | 2) PLEASE PROVIDE THE RATING OF THE ELEVATOR LOBBY |
| | WALLS AND PROVIDE RATED DAMPERS FOR ALL DUCTWORK |
| | PENETRATING THESE WALLS, ALSO PLEASE SHOW HOW THE |
| | RETURN FROM THE 8TH FLOOR ELEVATOR LOBBY WILL FLOW BACK |
| | OUT OF THE ELEVATOR LOBBY. FMC 607. |
| | |
| | 3) ALL OF THE DUCTWORK AT THE RATED SHAFTS; EXISTING |
| | SMOKE EXHAUST, EXISTING OA/SMOKE PRESSURIZATION AND THE |
| | EXISTING EXHAUST RISER, ON BOTH FLOORS SHOULD HAVE |
| | FIRE/SMOKE DAMPERS AT THE SHAFT PENETRATION. FMC 607 |
| | |
| | 4) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH |
| | USE OF SPACE AND NOT BY THE WSHP. EACH USE OF SPACE |
| | SHOULD BE CALCULATED USING FMC 403.3.1.1 3RD SENTENCE |
| | AND TABLE 403.3.1.1. PLEASE PROVIDE THE OCCUPANCY |
| | CLASSIFICATION THAT MOST CLOSELY REPRESENTS EACH USE OF |
| | SPACE FROM TABLE 403.3.1.1. EXAMPLE: A CONFERENCE ROOM |
| | IS CALCULATED DIFFERENTLY THAN AN OFFICE. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |