| Plan Review Notes For Permit 22030326 |
| Permit Number |
22030326 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-07-06 10:51:06 | CONSIDER THE FOLLOWING COMMENTS AS PROVISO | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | INSTALATION OF FIRE SPRINKLER SYSTEM IS REQUIRED TO BE | | | COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR AND | | | SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, ARE | | | REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE | | | FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM. | | | | | | PLEASE ADDRESS FIRE SPRINKLERS MORE SPECICALLY IN PLAN | | | SET. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] |
|