| 2022-04-20 14:50:28 | BUILD OUT |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE SHOW THE RAMP HEIGHT TO COMPLY WITH FBC 405.6 |
| | RISE. THE RISE FOR ANY RAMP RUN SHALL BE 30 INCHES (760 |
| | MM) MAXIMUM. |
| | |
| | 2) RAMP IS SUBJECT TO WIND LOADS - PLEASE PROVIDE RAMP |
| | DETAILS FROM A DESIGN PROFESSIONAL - SHOWING THE |
| | FOUNDATION, TIE DOWNS AND THE WIND DESIGN DATA USED - |
| | FBC 1603.1.4 |
| | |
| | 3) PLEASE SHOW THE WIND DESIGN DATA USED ON THE |
| | DRAWINGS FBC 1603.1.4 |
| | |
| | 4) PLEASE SHOW THE CALCULATIONS FOR THE EXTERIOR |
| | OPENINGS THAT ARE CLOSE TO THE PROPERTY LINES FBC E |
| | 1012.6.3 OPENING PROTECTIVES. |
| | OPENINGS IN EXTERIOR WALLS SHALL BE PROTECTED AS |
| | REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING. WHERE |
| | OPENINGS IN THE EXTERIOR WALLS ARE REQUIRED TO BE |
| | PROTECTED BECAUSE OF THEIR DISTANCE FROM THE LOT LINE, |
| | THE SUM OF THE AREA OF SUCH OPENINGS SHALL NOT EXCEED |
| | 50 PERCENT OF THE TOTAL AREA OF THE WALL IN EACH STORY. |
| | |
| | 5) PLEASE SHOW THE EXISTING OCCUPANCY CLASSIFICATION |
| | FBC E 1012.6 |
| | |
| | 6) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE NEW EXTERIOR DOORS, EXTERIOR |
| | WINDOWS, ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED |
| | TO BE REVIEWED AND APPROVED BY THE DESIGNER OF RECORD |
| | FBC WPB 107.3.4 |
| | |
| | 7) ACCESSIBLE RESTROOMS - PLEASE STATE THAT THE MIRROR |
| | DIMENSIONS FROM THE FLOOR ARE TO THE "REFLECTIVE |
| | SURFACE" - FBC A 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 8) ACCESSIBLE RESTROOM - PLEASE SHOW THE REAR GRAB BAR |
| | DIMENSIONS FROM THE CENTER OF THE TOILET NOT THE WALL - |
| | FBC A 604.5.2 REAR WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | 9) ACCESSIBLE RESTROOM - PLEASE SHOW THE DIMENSION FOR |
| | THE TOILET PAPER HOLDER FROM THE FACE OF THE TOILET - |
| | FBC 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. |
| | |
| | 10) ACCESSIBLE SHOWER - PLEASE SHOW GRAB BARS ON ALL |
| | WALLS PER FBC 608.3.2 STANDARD ROLL-IN TYPE SHOWER |
| | COMPARTMENTS. |
| | WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE |
| | SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE |
| | BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB |
| | BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT |
| | IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER |
| | COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE |
| | WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES (150 MM) |
| | MAXIMUM FROM ADJACENT WALLS. |
| | |
| | 11) CANOPY DETAILS, ALUMINUM RAMP DETAILS, AND PRODUCT |
| | APPROVALS FOR WINDOWS, DOORS AND ROOFING SYSTEMS - ETC. |
| | MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS TO BE |
| | DEFERRED ON THE CONSTRUCTION DOCUMENTS - 107.3.4.1 |
| | DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, |
| | DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF |
| | THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED |
| | SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL |
| | REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL |
| | WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | |