| 2022-03-28 13:09:47 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH AND INCLUDE THE SQUARE FOOTAGE OF THE |
| | FLAT ROOF AREAS TO RECEIVE NEW ROOFING REPAIR (AS PER |
| | MOISTURE SURVEY) ALONG WITH THE TOTAL SQUARE FOOTAGE OF |
| | THE FLAT ROOF. PROVIDE THE PRODUCT APPROVAL/NOA FOR THE |
| | ROOFING SYSTEM TO BE USED FOR THE REPAIR. IF USING |
| | SUBMITTED PRODUCT APPROVAL FL14083-R27 PROVIDE SYSTEM |
| | NUMBER TO BE USED ALONG WITH THE INSTALLATION |
| | INSTRUCTIONS PAGE. REVISE ENGINEERED SIGNED AND SEALED |
| | NAILING CALCULATIONS TO INCLUDE ADDED SYSTEM IF |
| | APPLICABLE. |
| | 2. FBC EB 706.6 PROVIDE A FLASHING DETAIL DRAWING FOR |
| | THE EXISTING PARAPET WALLS TO INCLUDE PARAPET WALL |
| | HEIGHT(S). SECOND REQUEST. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |