| Plan Review Notes For Permit 22030315 |
| Permit Number |
22030315 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-23 17:26:31 | INSUFFICIENT | | | | | | 1) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED | | | SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, THE | | | SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY ALONG | | | THE ENTIRE FIBER CONDUIT PATH SO THAT STAFF CAN VERIFY | | | THAT THE BORE, OPEN TRENCH AND ANY REQUIRED BORE PITS | | | AND HANDHOLES ARE WITHIN THE RIGHT-OF-WAY. THE SURVEY | | | NEEDS TO INCLUDE THE LOCATION OF PROPOSED HANDHOLES | | | 00+00, 07+90, 13+00 BORE PIT 04+00, THE OPEN TRENCH AND | | | THE BORE SECTION ALONG THE WEST SIDE OF BROADWAY SO | | | THAT STAFF CAN VERIFY THAT THE PROPOSED WORK IS | | | EXCLUSIVELY WITHIN FDOT RIGHT-OF-WAY AND NOT ON PRIVATE | | | PROPERTY. IN ORDER TO INSTALL HANDHOLES AND BORE UNDER | | | PRIVATE PROPERTY IS MUST BE IN A GENERAL UTILITY | | | EASEMENT. THIS GENERAL UTILITY EASEMENT MUST BE CLEARLY | | | SHOWN ON THE SURVEY. | | | | | | 2) THE TUBULAR MARKERS ARE NOT PERMITTED. MARKERS MAY | | | ONLY BE INSTALLED WITHIN THE HANDHOLES OR OTHERWISE | | | BURIED. | | | | | | 3) THE BORE DEPTH IS SUFFICIENT TO AVOID TREE ROOTS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|