| Plan Review Notes For Permit 22030314 |
| Permit Number |
22030314 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-07-16 08:21:53 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGES E2.5 AND E2.6 SHOW CAR CHARGERS BUT ON PANEL | | | SCHEDULE THEY ARE SHOWN AS FUTURE? PLEASE COORDINATE. | | | | | | AGAIN VALUE FOR NEW HPACC PANEL AND THE CHARGERS 22,5K | | | | | | PAGE E7.7 WHICH CARGER ARE YOU USING? SPECS DO NOT LIST | | | ELECTRICAL REQUIREMENTS FOR THE CHARGERS. | | | | | | PAGE E7.6 PANEL HPACC LOAD FOR CAR CHARGERS ARE TO BE | | | DONE AT 125% 625.41 | | | | | | |
|