| 2022-05-03 13:34:09 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22030314 |
| | 5/2/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| | |
| | 1) FAILED. PLEASE REVISE THE PLUMBING FIXTURE SCHEDULE |
| | TO INCLUDE THE NEW DRINKING FOUNTAIN- SEC. 107.2.1 WPB. |
| | NOT PROVIDED. |
| | |
| | 2) FAILED.REVISE THE ARCHITECTURAL PLANS TO SHOW THE |
| | LOCATION OF THE DRINKING FOUNTAIN AND REQUIRED |
| | ACCESSIBILITY COMPLIANCES- SEC. 107.2.1 WPB. THE |
| | DRAWINGS APPEAR TO SHOW ONLY THE WHEELCHAIR ACCESSIBLE |
| | DRINKING FOUNTAIN. PLEASE NOTE THAT NO FEWER THAN TWO |
| | DRINKING FOUNTAINS SHALL BE PROVIDED- ONE SHALL COMPLY |
| | WITH 602.1 (LO) AND ONE SHALL COMPLY WITH 602.7 (HI)- |
| | SEC. 211.2 FBC ACC. |
| | |
| | FAILED. DRINKING FOUNTAINS: REFER TO SECS. 306, 307, |
| | AND 602 FBC ACC AND PROVIDE AN ELEVATION VIEW OF THE |
| | FOUNTAIN SHOWING KNEE AND TOE CLEARANCES AND SPOUT |
| | HEIGHTS. SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR |
| | SPACE FOR A FORWARD WHEELCHAIR APPROACH TO THE |
| | FOUNTAIN- SEC. 602.2 FBC ACC. SHOW HOW THE LOCATIONS OF |
| | THE FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2 |
| | PROTRUSION LIMITS. COMPLIANCE DETAILS NOT PROVIDED. |
| | |
| | NEW COMMENTS ON RESUBMITTED PLANS. |
| | |
| | 1) REVISE SHEET P.20A TO SHOW THE UNDERGOUND PLUMBING |
| | DRAINS FOR THE NEW DRINKING FOUNTAINS- SEC. 107.2.1 |
| | WPB. |
| | |
| | 2) P.20A: PLACE A NOTE TO INDICATE THE WATER HEATER |
| | DRAIN PAN LINES WILL DISCHARGE TO EITHER PERMEABLE |
| | GROUND OR A DRY WELL, AND THE DRAIN PIPE SHALL |
| | DISCHARGE NOT LESS THAN 12-INCHES AWAY FROM THE |
| | BUILDING AT A POINT NO LESS THAN 6-INCHES AND NO MORE |
| | THAN 24-INCHES ABOVE THE GROUND SURFACE- SEC. 504.7.2 |
| | FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |