| 2022-03-16 10:40:06 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22030309 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE CLEAN UP THIS DRAWING AS THE REVIEWER IS | | | HAVING A HARD TIME MAKING OUT SOME OF THE ROOMS AND | | | PLACEMENT OF THE DUCTWORK. IT APPEARS THAT WALLS | | | SEPARATING THE ROOMS HAVE NO DOORS TO THE ROOMS. IT | | | ALSO APPEARS THAT THE KITCHEN HOOD IS VENTING IN THE | | | SAME EXHAUST DUCT AS THE BATH EXHAUST. THERE IS A BATH | | | EXHAUST FAN IN THE BEDROOM-2. PLEASE SHOW THE | | | CONDENSATE DRAIN LINES AND TERMINATION LOCATIONS. FBC | | | 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|