| 2022-04-25 16:10:07 | 3RD REVIEW FMC |
| | PERMIT: 22030298 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE CONSISTENT DOCUMENTS. THE MECHANICAL |
| | EQUIPMENT SIZING CALCULATIONS ARE FOR A 2-TON DUCTLESS |
| | SYSTEM ? CHURCH FOOD STORAGE. THE ENERGY CALCULATIONS |
| | ALSO SHOW 1 2-TON DUCTLESS HEAT PUMP. THE MECHANICAL |
| | DRAWINGS ARE BLURRY AND YOU CANNOT READ THE WRITING. |
| | PLEASE PROVIDE CLEAR DRAWINGS. THE MECHANICAL DRAWINGS |
| | ALSO SHOW A TOTAL OF 2 A/C UNITS, THIS DOES NOT MATCH |
| | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS. PLEASE |
| | SHOW THAT THESE A/C UNITS PROVIDE THE REQUIRED HEAT FOR |
| | THIS SPACE. THE MECHANICAL DRAWING IS TITLED CHURCH A/C |
| | SYSTEM PLEASE LABEL THIS DRAWING TO CLEARLY IDENTIFY |
| | WHERE THE SYSTEMS SILL BE LOCATED. PLEASE SHOW HOW THE |
| | REQUIRED OUTDOOR AIR WILL BE BROUGHT INTO THIS |
| | BUILDING. PLEASE PICK A DESIGN AND MAKE EVERYTHING |
| | SUBMITTED AS ONE SYSTEM. THERE ARE TOTALLY DIFFERENT |
| | DRAWINGS IN THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS THAN THE MECHANICAL DRAWING SUBMITTED. I |
| | CANNOT DO A REVIEW ON THIS PROJECT UNTIL THE DOCUMENTS |
| | ARE SUBMITTED CORRECTLY FOR ONE DESIGN. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |