Plan Review Notes
Plan Review Notes For Permit 22030298
Permit Number 22030298
Review Stop M
Sequence Number 3
Notes
Date Text
2022-04-25 16:10:073RD REVIEW FMC
 PERMIT: 22030298
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE CONSISTENT DOCUMENTS. THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS ARE FOR A 2-TON DUCTLESS
 SYSTEM ? CHURCH FOOD STORAGE. THE ENERGY CALCULATIONS
 ALSO SHOW 1 2-TON DUCTLESS HEAT PUMP. THE MECHANICAL
 DRAWINGS ARE BLURRY AND YOU CANNOT READ THE WRITING.
 PLEASE PROVIDE CLEAR DRAWINGS. THE MECHANICAL DRAWINGS
 ALSO SHOW A TOTAL OF 2 A/C UNITS, THIS DOES NOT MATCH
 THE MECHANICAL EQUIPMENT SIZING CALCULATIONS. PLEASE
 SHOW THAT THESE A/C UNITS PROVIDE THE REQUIRED HEAT FOR
 THIS SPACE. THE MECHANICAL DRAWING IS TITLED CHURCH A/C
 SYSTEM PLEASE LABEL THIS DRAWING TO CLEARLY IDENTIFY
 WHERE THE SYSTEMS SILL BE LOCATED. PLEASE SHOW HOW THE
 REQUIRED OUTDOOR AIR WILL BE BROUGHT INTO THIS
 BUILDING. PLEASE PICK A DESIGN AND MAKE EVERYTHING
 SUBMITTED AS ONE SYSTEM. THERE ARE TOTALLY DIFFERENT
 DRAWINGS IN THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS THAN THE MECHANICAL DRAWING SUBMITTED. I
 CANNOT DO A REVIEW ON THIS PROJECT UNTIL THE DOCUMENTS
 ARE SUBMITTED CORRECTLY FOR ONE DESIGN. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  