| Plan Review Notes For Permit 22030297 |
| Permit Number |
22030297 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-05-24 14:26:34 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT- 22030297 | | | 5/24/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) CORRECTED PLAN SHEETS A200 & A201: PROVIDE THE | | | FOLLOWING DETAILS PER FBC ACC: | | | | | | A) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED | | | FLOORS- SEC. 604.4. | | | | | | B) THE LENGTH MEASUREMENTS OF THE WATER CLOSET GRAB | | | BARS- SEC. 604.5. | | | | | | C) THE CENTERLINES OF THE TOILET PAPER DISPENSERS | | | MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND | | | FIGURE 604.7. | | | | | | D) THE HEIGHT MEASUREMENTS OF THE ROLL-IN SHOWER | | | THRESHOLD- SEC. 608.7. PLEASE NOTE THE SUBMITTAL FOR | | | THE SHOWER SHOWS A 4-INCH-HIGH THRESHOLD HOWEVER THE | | | MAXIMUM HEIGHT ALLOWABLE IS 1/2-INCH. THE SUBMITTAL | | | ALSO DOES NOT INDICATE THE SHOWER IS AN ADA COMPLIANT | | | MODEL. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|