| 2022-04-11 10:36:41 | ELECTRIC REVIEW FAILED | | | 1) THE CODE ANALYSYS SHEET STATES THIS IS A LEVEL 1 | | | ALTERATION, IT APPEARS FROM THE WORK SCOPE THAT THIS IS | | | A LEVEL 2 ALTERATION. PLEASE CLARIFY . FBC EXISTING | | | BUILDING 602.1 AND 603.1 | | | 2) IF CLASSIFIED AS A LEVEL 2 THEN ARC FAULT CIRCUIRT | | | PROTECTION SHALL BE REQUIRED AS WELL AS OTHER | | | REQUIREMENTS OF THE NEC AS REQUIRED. NEC 210.12 AND NEC | | | 2017 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|