| Plan Review Notes For Permit 22030266 |
| Permit Number |
22030266 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-11 10:19:39 | 1ST REVIEW FMC | | | PERMIT: 22030266 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) ENERGY CALCULATIONS: PAGE 19 OF 27 CALLS OUT THE | | | AREA FOR AHU-1 AS 913 SQ.FT. AND THE AREA FOR THE RTU-1 | | | IS 1460. PAGE 1 OF 2 FOR THE MECHANICAL EQUIPMENT | | | SIZING CALCULATIONS CALLS OUT 1318 SQ. FT. FOR THE | | | AHU-1 AND PAGE 2 OF 2 CALLS OUT 1460 SQ. FT. OF AREA | | | FOR THE RTU-1. PLEASE CORRECT THIS AS EACH SHOULD BE | | | BASED ON THE SAME SQ. FT. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|