| 2022-04-08 14:48:57 | ELECTRIC REVIEW FAILED |
| | 1) ELECTRIC RISER DOES NOT MATCH DETAILS ON ELECTRIC |
| | DRAWING. ELECTRIC DRAWING DETAILS A METER. PLEASE |
| | PROVIDE CORRECT DRAWING MATCHING CONDITIONS ON SITE. |
| | FBC 107.2 |
| | 2) LOAD CALCULATION DETAILS A 3000 WATT TANKLESS WATER |
| | HEATER AND PANEL SCHEDULE DETAILS A 50 AMP BREAKER. |
| | PLEASE PROVIDE TANKLESS WATER HEATER SPECS AND CORRECT |
| | DRAWING ACCORDINGLY. FBC 107.2 |
| | 3) DRYER IN LOAD IS LISTED AT 1,800 WATTS. NEC STATES |
| | DRYER LOAD SHALL BE 5,000 WATTS OR NAME PLATE WHICH |
| | EVER IS LARGER.PLEASE CORRECT AS PER NEC 220.54 |
| | 4) ELECTRIC RISER DETAILS A 175-AMP MAIN BREAKER IN A |
| | 150- AMP RATED PANEL . OVER CURRENT PROTECTION FOR A |
| | PANEL BOARD CANNOT BE GREATER THAN THE PANEL BOARD |
| | RATING. NEC 408.36 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |