| 2022-04-30 08:41:30 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | BU1635 BN4338 |
| | ASFPM CFM US-21-11935 |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT |
| | APPROVAL OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 |
| | FBC, FOR THE PROPOSED WINDOWS AND DOORS. |
| | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, |
| | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | NOTICE: VERIFY EGRESS AT NEW SLEEPING ROOM. |
| | |
| | R310.2.1MINIMUM OPENING AREA. |
| | |
| | EMERGENCY AND ESCAPE RESCUE OPENINGS SHALL HAVE A NET |
| | CLEAR OPENING OF NOT LESS THAN 5.7 SQUARE FEET (0.530 |
| | M2). THE NET CLEAR OPENING DIMENSIONS REQUIRED BY THIS |
| | SECTION SHALL BE OBTAINED BY THE NORMAL OPERATION OF |
| | THE EMERGENCY ESCAPE AND RESCUE OPENING FROM THE |
| | INSIDE. THE NET CLEAR HEIGHT OPENING SHALL BE NOT LESS |
| | THAN 24 INCHES (610 MM) AND THE NET CLEAR WIDTH SHALL |
| | BE NOT LESS THAN 20 INCHES (508 MM). |
| | |
| | EXCEPTION: GRADE FLOOR OR BELOW GRADE OPENINGS SHALL |
| | HAVE A NET CLEAR OPENING OF NOT LESS THAN 5 SQUARE FEET |
| | (0.465 M2). |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |