| Plan Review Notes For Permit 22030212 |
| Permit Number |
22030212 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-08 13:08:10 | FIRE PROVISO: | | | | | | FIRE SPRINKLER PIPE INSPECTION ALSO REQUIRED | | | CODE: 603 | | | | | | TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13 | | | | | | CONTRACTOR TO PROVIDE FOR WORKING PRESSURE VERIFICATION | | | (I.E. PRESSURE GAUGE 2HRS) | | | AND/OR SYSTEM IS CHARGED/DISCHARGED UNDER WORKING | | | PRESSURE. (I.E. VISUAL FOR LEAKS | | | & INSPECTOR DRAIN AFTER 2 HRS) | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|