Plan Review Notes
Plan Review Notes For Permit 22030211
Permit Number 22030211
Review Stop M
Sequence Number 1
Notes
Date Text
2022-03-17 10:37:331ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22030211
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M.1 AND M.2: AHU-2 ON THE SPLIT SYSTEM
 SCHEDULE AHU-1 IS REFERENCING AREA SERVED AS 1ST FLOOR
 LIVING AND AHU-2 AS 2ND FLOOR BEDROOMS. THIS PROJECT IS
 A SINGLE STORY DUPLEX SO PLEASE IDENTIFY THESE AHU?S AS
 SERVING THE DUPLEX UNITS. FBC 107.2.1
  
 2) PLEASE IDENTIFY THE DUCT SIZE OF THE MAIN TRUNK LINE
 AND THE DUCT SUPPLYING THE WALK-IN CLOSET IN EACH UNIT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  