| Plan Review Notes For Permit 22030211 |
| Permit Number |
22030211 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-17 10:37:33 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22030211 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS M.1 AND M.2: AHU-2 ON THE SPLIT SYSTEM | | | SCHEDULE AHU-1 IS REFERENCING AREA SERVED AS 1ST FLOOR | | | LIVING AND AHU-2 AS 2ND FLOOR BEDROOMS. THIS PROJECT IS | | | A SINGLE STORY DUPLEX SO PLEASE IDENTIFY THESE AHU?S AS | | | SERVING THE DUPLEX UNITS. FBC 107.2.1 | | | | | | 2) PLEASE IDENTIFY THE DUCT SIZE OF THE MAIN TRUNK LINE | | | AND THE DUCT SUPPLYING THE WALK-IN CLOSET IN EACH UNIT. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|