| Notes |
| Date |
Text |
| 2022-08-24 10:39:26 | INSUFFICIENT | | | | | | 1) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED | | | SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, THE | | | SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY ALONG | | | THE ENTIRE FIBER CONDUIT PATH SO THAT STAFF CAN VERIFY | | | THAT THE BORE, OPEN TRENCH AND ANY REQUIRED BORE PIT | | | AND HANDHOLES ARE WITHIN THE RIGHT-OF-WAY. THE SURVEY | | | NEEDS TO INCLUDE THE LOCATION OF PROPOSED HANDHOLES | | | 00+74 AND 04+74, THE OPEN TRENCH AND THE BORE SECTION | | | ALONG THE SOUTH DIXIE HIGHWAY SO THAT STAFF CAN VERIFY | | | THAT THE PROPOSED WORK IS EXCLUSIVELY WITHIN FDOT | | | RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY. IN ORDER TO | | | INSTALL HANDHOLES AND BORE UNDER PRIVATE PROPERTY IS | | | MUST BE IN A GENERAL UTILITY EASEMENT. THIS GENERAL | | | UTILITY EASEMENT MUST BE CLEARLY SHOWN ON THE SURVEY. | | | | | | 2) THE FINK MARKERS ARE NOT PERMITTED. MARKERS MAY ONLY | | | BE INSTALLED WITHIN THE HANDHOLES OR OTHERWISE BURIED. | | | | | | 3) THE BORE DEPTH IS SUFFICIENT TO AVOID TREE ROOTS. | | | | | | 4) THE STREETLIGHT ADJACENT TO HANDHOLE 10+74 MUST BE | | | SHOWN ON THE PLANS SO THAT STAFF CAN VERIFY THAT THERE | | | IS NO CONFLICT WITH THE LIGHT POLE. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | | | | | | | |
|