| 2022-05-03 17:14:37 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22030091 |
| | ADD: 3705 S. FLAGLER DR. # 28 |
| | CONT: ROBERT P RUBINO INC |
| | TEL: 561-445-2010 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MAY 3RD/ 2022 |
| | ACTION: DENIED |
| | |
| | MISSING PLAN REVIEW ITEMS. 2020 W. P. B. ADMINISTRATIVE |
| | CODE107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATIVE CODE SECTION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| | OR STRUCTURES. |
| | 107.3.5.1 COMMERCIAL BUILDINGS |
| | 107.3.5.1.1. BUILDING |
| | MISSING CODE DATA: |
| | |
| | 1) SITE PLAN WITH LAYOUT, FOOTPRINT OF BUILDING WITH |
| | UNIT LOCATION IN THE BUILDING IN RELATION TO THE |
| | INTERCOASTAL WATERWAY. |
| | |
| | 2.1) FLOOR PLAN OF UNIT WITH WINDOWS AND OR DOORS TO BE |
| | REPLACED & OPENING SCHEDULE WITH PRESSURES . |
| | |
| | 2.2 CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE |
| | CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF |
| | PLANS AND OR SCHEDULES WILL NEED TO IDENTIFY THEMSELVES |
| | AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, |
| | SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE |
| | LICENSED IN AND PLANS AND OR SCHEDULES DRAWN. |
| | |
| | 3) MISSING WINDOW AND OR DOOR PRODUCT APPROVAL. |
| | |
| | 4) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE |
| | OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 5) 2020 FBC-B 1603.1.4 WIND DESIGN DATA, BY A ENGINEER. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 5.2. RISK CATEGORY. |
| | |
| | 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1. |
| | |
| | 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 5.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | |
| | 5.7) 2020 FBC-B 1709.5.1 HABITAT SPACES, WATER |
| | INTRUSION. EXTERIOR DOORS AND WINDOWS. EXCEPTION # 2. |
| | SILL LIMITING FACTOR. |
| | |
| | 6) 2020 FBC-BUILDING 1609.4.3. EXPOSURE CATEGORIES, |
| | EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND |
| | SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D, |
| | PREVAILS IN THE UPWARD DIRECTION FOR A DISTANCE OF AT |
| | LEAST 5,000 FEET OR 20 TIMES THE HEIGHT OF THE |
| | BUILDING, WHICHEVER IS GREATER. EXPOSURE SHALL ALSO |
| | APPLY WHERE THE GROUND SURFACE ROUGHNESS IMMEDIATELY |
| | UPWIND OF THE SITE IS B OR C , AND THE SITE IS WITHIN A |
| | DISTANCE OF 600 FEET OR 20 TIMES THE BUILDING HEIGHT, |
| | WHICHEVER IS GREATER, FROM AN EXPOSURE D CONDITION AS |
| | DEFINED IN THE PREVIOUS SENTENCE. |
| | |
| | 7 A TRANSMITTAL LETTER / NARRATIVE LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |