2022-05-20 10:27:45FIRE PROVISO NOTE:
 A WARNING SIGN, WITH MINIMUM ? INCH (6 MM) LETTERS,
 SHALL BE AFFIXED ADJACENT TO THE MAIN SHUTOFF VALVE AND
 SHALL STATE THE FOLLOWING:
 WARNING: THE WATER SYSTEM FOR THIS HOME SUPPLIES FIRE
 SPRINKLERS THAT REQUIRE CERTAIN FLOWS AND PRESSURES TO
 FIGHT A FIRE. DEVICES THAT RESTRICT THE FLOW OR
 DECREASE THE PRESSURE OR AUTOMATICALLY SHUT OFF THE
 WATER TO THE FIRE SPRINKLER SYSTEM, SUCH AS WATER
 SOFTENERS, FILTRATION SYSTEMS, AND AUTOMATIC SHUTOFF
 VALVES, SHALL NOT BE ADDED TO THIS SYSTEM WITHOUT A
 REVIEW OF THE FIRE SPRINKLER SYSTEM BY A FIRE
 PROTECTION SPECIALIST. DO NOT REMOVE THIS SIGN.