| 2022-03-09 08:33:48 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 22030035 |
| | 3/9/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P6.1: REVISE THE 2 PSI SYSTEM TOTAL LOAD OF |
| | 1,776,000 BTU TO INCLUDE THE 1,473,000 BTU LOAD OF THE |
| | GENERATOR- SEC. 402.2 FBC FG. |
| | |
| | 2) SHEETS P3.1 & P6.1: REFER TO TABLE 492.4(5) FBC FG- |
| | THE MAIN SUPPLY PIPE FROM THE METER TO THE 1ST TEE |
| | SHALL BE MINIMUM 1-1/2 FOR THE TOTAL BTU LOAD OF |
| | 3,249,000 AT A DEVELOPED SYSTEM LENGTH OF 141 FT.- SEC. |
| | 402.4.1 FBC FG. |
| | |
| | 3) P3.1 & P6.1: IT APPEARS THAT THE NEW GAS PIPE TO THE |
| | GENERATOR WILL BE RUN UNDERGROUND. PLEASE SPECIFY THE |
| | TYPE OF PIPING AND PROVIDE THE PIPE SIZING TABLE USED- |
| | SECS. 402.3 & 403.1 FBC FG. |
| | |
| | 4) P3.1 & P6.1: PLEASE PLACE A NOTE TO INDICATE THE |
| | GENERATOR INSTALLATION SHALL BE DONE UNDER A SEPARATE |
| | PERMIT- SECS. 105.1 & 107.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |