| Plan Review Notes For Permit 22030028 |
| Permit Number |
22030028 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-28 11:17:46 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, THE OPENING SCHEDULE NEEDS TO BE | | | CORRECTED FOR OPENING #5 BOTTOM CONNECTION (H) | | | FASTENING SPACING SHOULD BE AT 7" O.C PER PRODUCT | | | APPROVAL # FL1850-R14 SHEET 13 OF 20 ANCHOR SPACING | | | TABLE. | | | | | | FBC B 107.2.1, A PRODUCT APPROVAL IS REQUIRED FOR THE | | | PROPOSED WINDOW TO BE INSTALLED. | | | FBC B 107.2.1, THERE IS NO INFORMATION ON THE OPENING | | | SCHEDULE FOR OPENING # 8 WINDOW. IF THIS WINDOW IS | | | INCLUDED IN ANOTHER PERMIT, ADD A NOTE REFERING TO THAT | | | PERMIT NUMBER. |
|