| 2022-03-22 09:24:25 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22030012 |
| | ADD: 819 8TH STREET |
| | CONT: NEWBOLD CONSTRUCTION |
| | TEL: 561-644-5764 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MARCH 22ND/2022 |
| | ACTION: DENIED |
| | |
| | 1) SEE ZONING COMMENTS 1, 2,& 3 SEPARATE PERMIT ARE |
| | REQUIRED FOR FENCE PERMIT, LANDSCAPING PERMIT , |
| | IRRIGATION PERMIT & RESTRIPING OF PARKING LOT. |
| | |
| | 2) SHEET D1 FOR ALL WINDOWS 1-18 (SINGLE SECTION) THE |
| | STATEMENT EXISTING WINDOWS ARE NON-IMPACT WINDOWS TO BE |
| | REMOVED AND WALL TRIMMED BELOW FOR NEW SILL HEIGHT OF |
| | 36 INCHES. ARE THESE WINDOWS TO BE RE-USED? IF SO HOW |
| | WILL THEY MEET THE REQUIREMENT IN THE 2020 FBC-BUILDING |
| | CODE 1609.1.2.2 LARGE MISSILE IMPACT OR 1609.1.2.4. |
| | |
| | 3) BOTH THE NOA 20-0428.01 4200/6200 ALUM. FIXED FRAME |
| | L. M. I. AND NOA 20-0814.10 CLIPPED EXTRUDED ALUM. TUBE |
| | MULLION W/ AND W/O STEEL REINFORCEMENT ARE MISSING |
| | COMPLIANCE WITH IDENTIFY GLAZING/ MULLIONS. PLEASE |
| | IDENTIFY IN THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| | DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 4) PLEASE NOTE THE ENGINEERING CALCULATIONS WERE SEALED |
| | WITH AN ENGINEERS SEAL FROM SOUTH CAROLINA. FLORIDA |
| | STATUTE 471.003?QUALIFICATIONS FOR PRACTICE; |
| | EXEMPTIONS. ? |
| | (1)?NO PERSON OTHER THAN A DULY LICENSED ENGINEER SHALL |
| | PRACTICE ENGINEERING OR USE THE NAME OR TITLE OF |
| | ?LICENSED ENGINEER,? ?PROFESSIONAL ENGINEER,? OR ANY |
| | OTHER TITLE, DESIGNATION, WORDS, LETTERS, |
| | ABBREVIATIONS, OR DEVICE TENDING TO INDICATE THAT SUCH |
| | PERSON HOLDS AN ACTIVE LICENSE AS AN ENGINEER IN THIS |
| | STATE. |
| | |
| | 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |