| 2022-04-14 08:23:09 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22021436 |
| | 4/14/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENT #1 FROM THE 1ST |
| | REVIEW COPIED BELOW STILL EXISTS- PLEASE COMPLY. |
| | |
| | 1) FAILED P-001: THE WATER HEATER THERMOSTAT CANNOT |
| | SERVE AS THE TEMPERATURE LIMITING MEANS FOR HOT WATER |
| | SUPPLIES TO THE MOP SINK AND BREAK ROOM SINK. PLEASE |
| | PROVIDE EITHER A MASTER THERMOSTATIC MIXING VALVE OR |
| | MIXING VALVES AT EACH FIXTURE- SEC. 607.1.1 FBC P. THE |
| | WATER HEATER DETAIL DOES NOT SHOW A MASTER THERMOSTATIC |
| | MIXING VALVE AND INDIVIDUAL MIXING VALVES WERE NOT |
| | PROVIDED AT THE MOP AND KITCHENETTE SINKS. IF USING A |
| | MASTER VALVE PLEASE SEE SECTION 607.2.2: THE HOT WATER |
| | OR TEMPERED WATER RETURN LINE SHALL BE ROUTED TO THE |
| | COLD WATER INLET PIPE OF THE WATER HEATER AND THE COLD |
| | WATER INLET PIPE OR THE HOT WATER RETURN CONNECTION OF |
| | THE THERMOSTATIC MIXING VALVE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |