2022-04-14 08:23:092ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22021436
 4/14/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #1 FROM THE 1ST
 REVIEW COPIED BELOW STILL EXISTS- PLEASE COMPLY.
  
 1) FAILED P-001: THE WATER HEATER THERMOSTAT CANNOT
 SERVE AS THE TEMPERATURE LIMITING MEANS FOR HOT WATER
 SUPPLIES TO THE MOP SINK AND BREAK ROOM SINK. PLEASE
 PROVIDE EITHER A MASTER THERMOSTATIC MIXING VALVE OR
 MIXING VALVES AT EACH FIXTURE- SEC. 607.1.1 FBC P. THE
 WATER HEATER DETAIL DOES NOT SHOW A MASTER THERMOSTATIC
 MIXING VALVE AND INDIVIDUAL MIXING VALVES WERE NOT
 PROVIDED AT THE MOP AND KITCHENETTE SINKS. IF USING A
 MASTER VALVE PLEASE SEE SECTION 607.2.2: THE HOT WATER
 OR TEMPERED WATER RETURN LINE SHALL BE ROUTED TO THE
 COLD WATER INLET PIPE OF THE WATER HEATER AND THE COLD
 WATER INLET PIPE OR THE HOT WATER RETURN CONNECTION OF
 THE THERMOSTATIC MIXING VALVE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  