| 2022-04-04 15:30:26 | ELECTRIC REVIEW FAILED |
| | 1) ROOM LABELED IT/STORAGE ENCLOSES ELECTRIC PANEL |
| | WHERE NO STORAGE IS ALLOWED AS PER. PLEASE REMOVE |
| | STORAGE FROM THIS ROOM LABEL. NEC 110.26 (B) |
| | 2) PLEASE INCLUDE A NOTE THAT SEPARATE PERMITS ARE |
| | REQUIRED FOR, LOW VOLTAGE, FIRE ALARM, ACCESS CONTROL |
| | 3) PLEASE ENSURE COMPLIANCE WITH NEC 210.71 (B)(1) |
| | RECEPTACLES REQUIRED ON FIXED WALLS IN MEETING ROOMS |
| | 4) CONDUCTOR SIZE ON PRIMARY SIZE OF TRANSFORMER IS |
| | SIZED INCORRECTLY AT #8 CU, PLEASE CORRECT CONDUCTOR |
| | SIZE TO A #6 CU AS PER NEC 110.14(C)(1)(2). TERMINATION |
| | OF CIRCUITS RATED 100-AMPERES OR LESS MUST BE SIZED |
| | USING 65 DEGREE C. |
| | 5) CONDUCTOR SIZE ON SECONDARY SIZE OF TRANSFORMER IS |
| | SIZED INCORRECTLY AT #2 CU, PLEASE CORRECT CONDUCTOR |
| | SIZE TO A #1 CU AS PER NEC 110.14(C)(1)(2). TERMINATION |
| | OF CIRCUITS RATED 100-AMPERES OR LESS MUST BE SIZED |
| | USING 65 DEGREE C. |
| | 6) PLANS DO NOT DETAIL MAIN BREAKER IN LOW VOLTAGE |
| | PANEL. PLEASE CORRECT AS PER NEC 408.36 |
| | 7) PLEASE DETAIL TRANSFORMER GROUNDING. FBC 107.2 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |