Plan Review Notes
Plan Review Notes For Permit 22021422
Permit Number 22021422
Review Stop P
Sequence Number 3
Notes
Date Text
2022-06-24 10:21:37 
 3RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22021422
 6/24/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS ARE LISTED
 BELOW WITH ADDITIONAL NOTES FOR CLARIFICATION.
  
 2H) FAILED- 2ND REQUEST. LOCATIONS, LENGTHS, AND
 MOUNTING HEIGHTS OF GRAB BARS FOR THE WATER CLOSETS-
 SEC. 604.5 & 609.4, FIGURES 604. PLEASE NOTE THE
 DETAILS SHOW THE HEIGHTS MEASURED TO THE CENTER OF THE
 BARS AND NOT THE TOPS OF THE SURFACES. THE SIDE GRAB
 BAR SHALL EXTEND A MINIMUM OF 54-INCHES FROM THE REAR
 WALL. THE DETAIL INDICATES 48-INCHES. PLEASE PROVIDE A
 CORRECT DETAIL FOR BOTH THE MEN?S AND WOMEN?S
 ACCESSIBLE COMPARTMENTS- FIGURES 604.5.1 & 604.5.2 FBC
 ACC.
  
 3) FAILED- 2ND REQUEST. P-101: PLEASE REMOVE NOTE 3 ON
 THE PLAN INDICATING AN ASSE 1070 APPROVED MIXING VALVE
 AT THE MOP SINK. HOT WATER IS REQUIRED AT THE MOP SINK,
 NOT TEMPERED WATER- SEC. 607.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  