| Plan Review Notes For Permit 22021422 |
| Permit Number |
22021422 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-06-27 08:59:54 | REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING IN-501 DETAIL D1 SHOWS TOILET SIDE GRAB BAR | | | LESS THEN THE REQUIRED 54 INCH FROM THE BACK WALL - FBC | | | A 604.5.1 SIDE WALL. | | | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) | | | LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM | | | THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM | | | FROM THE REAR WALL. | | | | | | | | | |
|