Plan Review Notes
Plan Review Notes For Permit 22021422
Permit Number 22021422
Review Stop B
Sequence Number 3
Notes
Date Text
2022-06-27 08:59:54REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING IN-501 DETAIL D1 SHOWS TOILET SIDE GRAB BAR
 LESS THEN THE REQUIRED 54 INCH FROM THE BACK WALL - FBC
 A 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
  
  