| 2022-05-25 10:20:55 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22021422 |
| | 5/25/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS ARE LISTED |
| | BELOW WITH ADDITIONAL NOTES FOR CLARIFICATION. |
| | |
| | 1) FAILED. SHEET IN-101.2: PLEASE REFER TO SECS. 202.3, |
| | 213.2 & 213.3.1 FBC ACC- THE NEW MEN?S AND WOMEN?S |
| | ACCESSIBLE TOILET COMPARTMENTS ARE UNDERSIZED PER SEC. |
| | 604.8.1. THE COMPARTMENTS SHALL BE MINIMUM 60-INCHES |
| | WIDE. PLEASE NOTE THAT SEC. 405.3.1 FBC P ALLOWS FOR |
| | THE STANDARD COMPARTMENTS TO BE MINIMUM 30-INCHES WIDE |
| | WHICH WOULD PROVIDE THE ADDITIONAL SPACE NEEDED TO MEET |
| | THE CODE FOR THE ACCESSIBLE COMPARTMENTS. |
| | THE RESUBMITTED PLANS SHOW THE ACCESSIBLE TOILET |
| | COMPARTMENTS REMAIN UNDERSIZED IN WIDTH. ACCESSIBILTY |
| | COMPLIANCE TO THE MAXIMUM EXTENT FEASIBLE- PLEASE SEE |
| | SECTION 202.3 EXCEPTION 2. AS PREVIOUSLY NOTED ABOVE |
| | THERE IS ADEQUATE SPACE TO PROVIDE THE REQUIRED WIDTH |
| | FOR THE COMPARTMENTS. |
| | |
| | 2) FAILED ITEMS BELOW SHEET IN-501: MISSING |
| | ACCESSIBILITY COMPLIANCE DETAILS PER FBC ACC- |
| | A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | THE WATER CLOSETS- SEC. 604.3.NOT PROVIDED. |
| | B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | THE LAVATORIES- SEC. 606.2. NOT PROVIDED. |
| | C) FAILED. TURNING SPACE DIAGRAMS AND DIMENSIONS- SEC. |
| | 304.3. NOT PROVIDED. |
| | D) FAILED. CENTERLINES OF THE WATER CLOSETS FROM THE |
| | SIDE WALLS- SEC. 604.2. NOT PROVIDED. |
| | E) FAILED. HEIGHTS OF THE WATER CLOSET SEATS FROM THE |
| | FINISHED FLOORS- SEC. 604.4. NOT PROVIDED. |
| | H) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| | GRAB BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, |
| | FIGURES 604. PLEASE NOTE THE DETAILS SHOW THE HEIGHTS |
| | MEASURED TO THE CENTER OF THE BARS AND NOT THE TOPS OF |
| | THE SURFACES. GRAB BAR MINIMUM LENGTHS AND SPACINGS NOT |
| | PROVIDED. |
| | J) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSERS |
| | MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND |
| | FIGURE 604.7. NOT PROVIDED. |
| | K) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES- |
| | SECTION 606.2 AND FIGURES 306.2 & 306.3. NOT PROVIDED. |
| | L) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | THE WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN- SEC. |
| | 602.2. NOT PROVIDED. |
| | M) FAILED. KNEE AND TOE CLEARANCES FOR THE WHEELCHAIR |
| | ACCESSIBLE DRINKING FOUNTAIN SEC. 602.2 AND FIGURES |
| | 306.2 & 306.3. NOT PROVIDED. |
| | N) FAILED. SPOUT HEIGHTS MEASURED FROM THE FINISHED |
| | FLOOR- SECS. 602.4 & 602.7. NOT PROVIDED. |
| | O) FAILED. SHOW DRINKING FOUNTAIN COMPLIANCE WITH SEC. |
| | 307.2 PROTRUSION LIMITS. NOT PROVIDED. |
| | |
| | 3) FAILED. P-101 & P-201: PROVIDE A MEANS OF LIMITING |
| | THE HOT WATER TEMPERATURE AT THE MOP SINK OTHER THAN |
| | THE THERMOSTAT CONTROL IN THE WATER HEATER- SEC. |
| | 607.1.1 FBC P. NOTE 3 ON THE PLAN SHOWS AN ASSE 1070 |
| | APPROVED MIXING VALVE AT THE MOP SINK. PLEASE NOTE THE |
| | ASSE 1070 MIXING VALVES DELIVER TEMPERED WATER BETWEEN |
| | 85 AND 110 DEGREES F. THE SPECIFIED VALVE SHALL BE FOR |
| | LIMITING HOT WATER TEMPERATURE AT 110 F AND ABOVE. |
| | |
| | 4) FAILED P-101 & P-102: INDICATE HOW TEMPERED WATER |
| | WILL BE DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC |
| | P. PLEASE NOTE THAT MIXING VALVES FOR TEMPERED WATER |
| | SHALL BE ASSE 1070 APPROVED- SEC. 607.1.2 FBC P. PLACE |
| | A NOTE TO INDIOCATE COLD WATER ONLY TO THE LAVATORIES |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |