| 2022-04-11 12:17:26 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22021422 |
| | 4/11/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET IN-101.2: PLEASE REFER TO SECS. 202.3, 213.2 & |
| | 213.3.1 FBC ACC- THE NEW MEN?S AND WOMEN?S ACCESSIBLE |
| | TOILET COMPARTMENTS ARE UNDERSIZED PER SEC. 604.8.1. |
| | THE COMPARTMENTS SHALL BE MINIMUM 60-INCHES WIDE. |
| | PLEASE NOTE THAT SEC. 405.3.1 FBC P ALLOWS FOR THE |
| | STANDARD COMPARTMENTS TO BE MINIMUM 30-INCHES WIDE |
| | WHICH WOULD PROVIDE THE ADDITIONAL SPACE NEEDED TO MEET |
| | THE CODE FOR THE ACCESSIBLE COMPARTMENTS. |
| | |
| | 2) SHEET IN-501: MISSING ACCESSIBILITY COMPLIANCE |
| | DETAILS PER FBC ACC- |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SEC. 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SEC. 606.2. |
| | C) TURNING SPACE DIAGRAMS AND DIMENSIONS- SEC. 304.3. |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SEC. 604.2. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SEC. 604.4. |
| | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SEC. 603.3 |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES |
| | 604. PLEASE NOTE THE DETAILS SHOW THE HEIGHTS MEASURED |
| | TO THE CENTER OF THE BARS AND NOT THE TOPS OF THE |
| | SURFACES. |
| | I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS ? SEC. |
| | 604.6. |
| | J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE |
| | 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2 AND FIGURES 306.2 & 306.3. |
| | L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN- SEC. 602.2. |
| | M) KNEE AND TOE CLEARANCES FOR THE WHEELCHAIR |
| | ACCESSIBLE DRINKING FOUNTAIN SEC. 602.2 AND FIGURES |
| | 306.2 & 306.3. |
| | N) SPOUT HEIGHTS MEASURED FROM THE FINISHED FLOOR- |
| | SECS. 602.4 & 602.7. |
| | O) SHOW DRINKING FOUNTAIN COMPLIANCE WITH SEC. 307.2 |
| | PROTRUSION LIMITS. |
| | |
| | 3) P-101 & P-201: PROVIDE A MEANS OF LIMITING THE HOT |
| | WATER TEMPERATURE AT THE MOP SINK OTHER THAN THE |
| | THERMOSTAT CONTROL IN THE WATER HEATER- SEC. 607.1.1 |
| | FBC P. |
| | |
| | 4) P-101 & P-102: INDICATE HOW TEMPERED WATER WILL BE |
| | DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC P. PLEASE |
| | NOTE THAT MIXING VALVES FOR TEMPERED WATER SHALL BE |
| | ASSE 1070 APPROVED- SEC. 607.1.2 FBC P |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |