2022-04-11 12:17:261ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22021422
 4/11/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET IN-101.2: PLEASE REFER TO SECS. 202.3, 213.2 &
 213.3.1 FBC ACC- THE NEW MEN?S AND WOMEN?S ACCESSIBLE
 TOILET COMPARTMENTS ARE UNDERSIZED PER SEC. 604.8.1.
 THE COMPARTMENTS SHALL BE MINIMUM 60-INCHES WIDE.
 PLEASE NOTE THAT SEC. 405.3.1 FBC P ALLOWS FOR THE
 STANDARD COMPARTMENTS TO BE MINIMUM 30-INCHES WIDE
 WHICH WOULD PROVIDE THE ADDITIONAL SPACE NEEDED TO MEET
 THE CODE FOR THE ACCESSIBLE COMPARTMENTS.
  
 2) SHEET IN-501: MISSING ACCESSIBILITY COMPLIANCE
 DETAILS PER FBC ACC-
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) TURNING SPACE DIAGRAMS AND DIMENSIONS- SEC. 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES
 604. PLEASE NOTE THE DETAILS SHOW THE HEIGHTS MEASURED
 TO THE CENTER OF THE BARS AND NOT THE TOPS OF THE
 SURFACES.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS ? SEC.
 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2 AND FIGURES 306.2 & 306.3.
 L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN- SEC. 602.2.
 M) KNEE AND TOE CLEARANCES FOR THE WHEELCHAIR
 ACCESSIBLE DRINKING FOUNTAIN SEC. 602.2 AND FIGURES
 306.2 & 306.3.
 N) SPOUT HEIGHTS MEASURED FROM THE FINISHED FLOOR-
 SECS. 602.4 & 602.7.
 O) SHOW DRINKING FOUNTAIN COMPLIANCE WITH SEC. 307.2
 PROTRUSION LIMITS.
  
 3) P-101 & P-201: PROVIDE A MEANS OF LIMITING THE HOT
 WATER TEMPERATURE AT THE MOP SINK OTHER THAN THE
 THERMOSTAT CONTROL IN THE WATER HEATER- SEC. 607.1.1
 FBC P.
  
 4) P-101 & P-102: INDICATE HOW TEMPERED WATER WILL BE
 DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC P. PLEASE
 NOTE THAT MIXING VALVES FOR TEMPERED WATER SHALL BE
 ASSE 1070 APPROVED- SEC. 607.1.2 FBC P
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719