2022-08-30 13:44:2322021416 222 LAKEVIEW AVE FL 10
  
 PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 PROVISO #1: PROVIDE LKAPREZL ELKAY CANE APRON FOR
 HIGHER DRINKING FOUNTAIN TO COMPLY WITH FBC ACC 307.2
  
 PROVISO #2: PER WPB FBC 107.2.1, A REVISED PLAN SHEET
 IN-501 SHALL BE SUBMITTED, APPROVED AND IN PLACE PRIOR
 TO FIRST INSPECTION. THE FOLLOWING DETAILS SHALL BE
 CORRECTED AS NOTED:
 D1; MAXIMUM HEIGHT TO TOP OF VANITY SHALL BE 34 INCHES
 (FBC ACC 606.3)
 D2; SIDE HANDRAIL SHALL BE 12 INCHES FROM REAR WALL AND
 A MINIMUM 54 INCHES OVERALL FROM REAR WALL (FBC ACC
 604.5.1)
 A3; MAXIMUM HEIGHT TO TOP OF VANITY SHALL BE 34 INCHES
 (FBC ACC 606.3)
  
 PROVISO #3: PER WPB FBC 107.2.1, A REVISED PLAN SHEET
 G001 GENERAL ACCESSIBILITY & ABBREVIATIONS PROVIDING A
 NOTE STATING THAT IN CASE OF DISCREPANCY BETWEEN PLAN
 SHEET G001 AND PLAN SHEETS IN501 L10 ENLARGED PLANS &
 ELEVATIONS, IN400 L10 WALL SECTIONS & DETAILS, IN101
 L10 ARCHITECTURAL PLAN, PLAN SHEETS IN501, IN400 AND
 IN101 SHALL PREVAIL. PLAN SHALL BE SUBMITTED, APPROVED
 AND IN PLACE PRIOR TO FIRST INSPECTION.
  