Plan Review Notes
Plan Review Notes For Permit 22021416
Permit Number 22021416
Review Stop P
Sequence Number 2
Notes
Date Text
2022-07-05 15:48:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22021416 222 LAKEVIEW AVE FL 10
  
 2ND REVIEW
  
 PROVISO #1: CONTRACTOR SHALL PROVIDE AS DEFERRED
 SUBMITTALS, MANUFACTURERS SPECIFICATION/INSTALLATION
 MANUAL FOR THE PLUMBING FIXTURES. SUBMITTAL SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION IN ACCORDANCE WITH WPB FBC 107.2.1 AND
 107.3.4.1. SEE IN101 L10 ARCHITECTURAL PLAN/GENERAL
 CONSTRUCTION NOTE R. PROCEED AT YOUR OWN RISK.
  
 PROVISO #2: A PLUMBING PRE-INSPECTION WILL BE REQUIRED
 ONCE THE WALLS ARE OPEN AND REVISED PLAN, SUBMITTED AND
 APPROVED, SHOWING NOTABLE CHANGES TO DESIGN AND ROUTING
 MAY BE REQUIRED BY THE PLUMBING INSPECTOR IN ACCORDANCE
 WITH WPB FBC 107.4. SEE IN101 L10 ARCHITECTURAL
 PLAN/GENERAL CONSTRUCTION NOTE T.
  
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6, REVISE PLAN SHEET G001 AND PROVIDE
 PLAN AND ELEVATION DETAILS FOR THE UPGRADED TOILET
 ROOMS INDICATING THE FOLLOWING:
 ***A) COMPLIED
 ***B) SECOND REQUEST:THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM
 FROM THE REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM
 THE REAR WALL PER FBC ACC 604.5.1
 TO BE CLEAR, REVISED IN501 L10 ENLARGED PLANS &
 ELEVATIONS/DETAIL D2 ADA STALL PARTION ELEVATION
 INDICATES 6 INCHES FROM REAR WALL TO SIDE HANDRAIL.
 PLEASE CORRECT, SHOWING 12 INCHES AND MINIMUM 54 INCHES
 MINIMUM OVERALL.
 ***C) COMPLIED
 ***D): COMPLIED
 ***E) COMPLIED
 ***F) COMPLIED
 ***G) COMPLIED
 ***H) COMPLIED
 ***I) COMPLIED
 ***J) PARTIALLY COMPLIED: DRINKING FOUNTAIN: PROVIDE
 ELEVATION AND CLEAR FLOOR SPACE SHOWING COMPLIANCE WITH
 FBC ACC 305, 306, 307 AND 602.
 REQUIREMENTS OF FBC ACC 307 NEED ATTENTION; SEE LINE
 ITEM ***K)
 ***K) SECOND REQUEST: DRINKING FOUNTAIN: FBC ACC 307.2;
 PROTRUDING OBJECTS AND PROTRUSION LIMITS. OBJECTS WITH
 LEADING EDGES MORE THAN 27 INCHES AND NOT MORE THAN 80
 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE MORE THAN 4
 INCHES HORIZONTALLY INTO THE CIRCULATION PATH.
  
 2.SECOND REQUEST:P-201/FIXTURE SCHEDULE: ELKAY LNTE8K
 DRINKING FOUNTAIN IS DISCONTINUED. PER WPB FBC 107.2.1,
 SPECIFY A DRINKING FOUNTAIN THAT IS CURRENTLY
 MANUFACTURED AND AVAILABLE.
 ENGINEER'S RESPONSE: REVISED SEE P-201. P-201 STILL
 LISTS THE LNTE8K.
 ARCHITECT'S RESPONSE: ADJUSTED SPEC. P-201 STILL LISTS
 THE LNTE8K.
  
 3.COMPLIANT
  
 4. COMPLIANT; SEE PROVISO #1
  
 5. COMPLIANT
  
 6.COMPLIANT
  
 7. COMPLIANT: SEE PROVISO #2
  
 NEW COMMENTS:
  
 1.NEW COMMENT: ENGINEER PROVIDED A RESPONSE STATING
 PLANS HAVE BEEN UPDATED WITH EXISTING PIPING AND THE
 PROPOSED CHANGES TO THE EXISTING PIPING.
 REVIEW OF PLANS REVEALS THE FOLLOWING: REVISED SEE
 P-001. REVIEW OF P-001/PLUMBING SHEET INDEX INDICATES
 REVISED P-101 SANITARY FLOOR PLAN AND ADDED P-102
 DOMESTIC FLOOR PLAN. P-101 IS STILL NOTED P-101
 PLUMBING PLAN, HAS NOT BEEN REVISED AND P-102 IS NOT
 AMONG THE SUBMITTED PLAN SHEETS. PER WPB FBC 107.2.1,
 PLEASE CLARIFY.
  
 2.NEW COMMENT: PLAN SHEET G001 GENERAL ACCESSIBILITY &
 ABBREVIATIONS: PER WPB FBC 107.2.1, PROVIDE A NOTE
 STATING THAT IN CASE OF DISCREPANCY BETWEEN PLAN SHEET
 G001 AND PLAN SHEETS IN501 L10 ENLARGED PLANS &
 ELEVATIONS, IN101 L10 ARCHITECTURAL PLAN, PLAN SHEETS
 IN501 AND IN 101 SHALL PREVAIL.
  
 3.NEW COMMENT: SEE REVISED IN501 L10 ENLARGED PLANS &
 ELEVATIONS/DETAIL A2; PER FBC ACC 606.3, LAVATORIES
 SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE
 RIM OR COUNTER SHALL BE 34 INCHES ABOVE THE FINUISH
 FLOOR OR GROUND, NOT 34-1/4 INCHES. PLEASE CORRECT.
  
 4.NEW COMMENT: PER WPB FBC 107.2.1, PLAN SHEET
 G-000/SHEET LIST SHALL REFLECT THE REVISED P-101
 SANITARY FLOOR PLAN AND ADDED P-102 DOMESTIC FLOOR PLAN
 INDICATED ON P-001/PLUMBING SHEET INDEX.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS