| 2022-07-05 15:48:51 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22021416 222 LAKEVIEW AVE FL 10 |
| | |
| | 2ND REVIEW |
| | |
| | PROVISO #1: CONTRACTOR SHALL PROVIDE AS DEFERRED |
| | SUBMITTALS, MANUFACTURERS SPECIFICATION/INSTALLATION |
| | MANUAL FOR THE PLUMBING FIXTURES. SUBMITTAL SHALL BE |
| | SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL |
| | INSPECTION IN ACCORDANCE WITH WPB FBC 107.2.1 AND |
| | 107.3.4.1. SEE IN101 L10 ARCHITECTURAL PLAN/GENERAL |
| | CONSTRUCTION NOTE R. PROCEED AT YOUR OWN RISK. |
| | |
| | PROVISO #2: A PLUMBING PRE-INSPECTION WILL BE REQUIRED |
| | ONCE THE WALLS ARE OPEN AND REVISED PLAN, SUBMITTED AND |
| | APPROVED, SHOWING NOTABLE CHANGES TO DESIGN AND ROUTING |
| | MAY BE REQUIRED BY THE PLUMBING INSPECTOR IN ACCORDANCE |
| | WITH WPB FBC 107.4. SEE IN101 L10 ARCHITECTURAL |
| | PLAN/GENERAL CONSTRUCTION NOTE T. |
| | |
| | PLUMBING COMMENTS: DENIED |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6, REVISE PLAN SHEET G001 AND PROVIDE |
| | PLAN AND ELEVATION DETAILS FOR THE UPGRADED TOILET |
| | ROOMS INDICATING THE FOLLOWING: |
| | ***A) COMPLIED |
| | ***B) SECOND REQUEST:THE SIDE WALL GRAB BAR SHALL BE 42 |
| | INCHES LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM |
| | FROM THE REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM |
| | THE REAR WALL PER FBC ACC 604.5.1 |
| | TO BE CLEAR, REVISED IN501 L10 ENLARGED PLANS & |
| | ELEVATIONS/DETAIL D2 ADA STALL PARTION ELEVATION |
| | INDICATES 6 INCHES FROM REAR WALL TO SIDE HANDRAIL. |
| | PLEASE CORRECT, SHOWING 12 INCHES AND MINIMUM 54 INCHES |
| | MINIMUM OVERALL. |
| | ***C) COMPLIED |
| | ***D): COMPLIED |
| | ***E) COMPLIED |
| | ***F) COMPLIED |
| | ***G) COMPLIED |
| | ***H) COMPLIED |
| | ***I) COMPLIED |
| | ***J) PARTIALLY COMPLIED: DRINKING FOUNTAIN: PROVIDE |
| | ELEVATION AND CLEAR FLOOR SPACE SHOWING COMPLIANCE WITH |
| | FBC ACC 305, 306, 307 AND 602. |
| | REQUIREMENTS OF FBC ACC 307 NEED ATTENTION; SEE LINE |
| | ITEM ***K) |
| | ***K) SECOND REQUEST: DRINKING FOUNTAIN: FBC ACC 307.2; |
| | PROTRUDING OBJECTS AND PROTRUSION LIMITS. OBJECTS WITH |
| | LEADING EDGES MORE THAN 27 INCHES AND NOT MORE THAN 80 |
| | INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 |
| | INCHES HORIZONTALLY INTO THE CIRCULATION PATH. |
| | |
| | 2.SECOND REQUEST:P-201/FIXTURE SCHEDULE: ELKAY LNTE8K |
| | DRINKING FOUNTAIN IS DISCONTINUED. PER WPB FBC 107.2.1, |
| | SPECIFY A DRINKING FOUNTAIN THAT IS CURRENTLY |
| | MANUFACTURED AND AVAILABLE. |
| | ENGINEER'S RESPONSE: REVISED SEE P-201. P-201 STILL |
| | LISTS THE LNTE8K. |
| | ARCHITECT'S RESPONSE: ADJUSTED SPEC. P-201 STILL LISTS |
| | THE LNTE8K. |
| | |
| | 3.COMPLIANT |
| | |
| | 4. COMPLIANT; SEE PROVISO #1 |
| | |
| | 5. COMPLIANT |
| | |
| | 6.COMPLIANT |
| | |
| | 7. COMPLIANT: SEE PROVISO #2 |
| | |
| | NEW COMMENTS: |
| | |
| | 1.NEW COMMENT: ENGINEER PROVIDED A RESPONSE STATING |
| | PLANS HAVE BEEN UPDATED WITH EXISTING PIPING AND THE |
| | PROPOSED CHANGES TO THE EXISTING PIPING. |
| | REVIEW OF PLANS REVEALS THE FOLLOWING: REVISED SEE |
| | P-001. REVIEW OF P-001/PLUMBING SHEET INDEX INDICATES |
| | REVISED P-101 SANITARY FLOOR PLAN AND ADDED P-102 |
| | DOMESTIC FLOOR PLAN. P-101 IS STILL NOTED P-101 |
| | PLUMBING PLAN, HAS NOT BEEN REVISED AND P-102 IS NOT |
| | AMONG THE SUBMITTED PLAN SHEETS. PER WPB FBC 107.2.1, |
| | PLEASE CLARIFY. |
| | |
| | 2.NEW COMMENT: PLAN SHEET G001 GENERAL ACCESSIBILITY & |
| | ABBREVIATIONS: PER WPB FBC 107.2.1, PROVIDE A NOTE |
| | STATING THAT IN CASE OF DISCREPANCY BETWEEN PLAN SHEET |
| | G001 AND PLAN SHEETS IN501 L10 ENLARGED PLANS & |
| | ELEVATIONS, IN101 L10 ARCHITECTURAL PLAN, PLAN SHEETS |
| | IN501 AND IN 101 SHALL PREVAIL. |
| | |
| | 3.NEW COMMENT: SEE REVISED IN501 L10 ENLARGED PLANS & |
| | ELEVATIONS/DETAIL A2; PER FBC ACC 606.3, LAVATORIES |
| | SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE |
| | RIM OR COUNTER SHALL BE 34 INCHES ABOVE THE FINUISH |
| | FLOOR OR GROUND, NOT 34-1/4 INCHES. PLEASE CORRECT. |
| | |
| | 4.NEW COMMENT: PER WPB FBC 107.2.1, PLAN SHEET |
| | G-000/SHEET LIST SHALL REFLECT THE REVISED P-101 |
| | SANITARY FLOOR PLAN AND ADDED P-102 DOMESTIC FLOOR PLAN |
| | INDICATED ON P-001/PLUMBING SHEET INDEX. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |