| Plan Review Notes For Permit 22021416 |
| Permit Number |
22021416 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-08-08 13:58:35 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | 2ND BUILDING REVIEW DENIED: | | | | | | PLEASE PROVIDE A RESPONSE SHEET TO THIS BUILDING REVIEW | | | AS IT APPEARS THAT THE FOLLOWING COMMENTS, FROM THE | | | FIRST REVIEW, BELOW HAVE NOT BEEN ADDRESSED. | | | | | | 1.) FBC B 107.2.1, FBC B 1004, ON PLAN SHEET LS 101 | | | (PROJECT DATA) COMPLETE THE OCCUPANCY SECTION. | | | 2.) FBC B 107.2.1, ON PLAN SHEET LS 101, (PROJECT DATA) | | | CORRECT THE EXISTING BUILDING CODE EDITION FROM 2020 | | | 6TH EDITION TO 2020 7TH EDITION. | | | 3.) FBC B 107.2.1, ON PLAN SHEET IN 801, COMPLETE THE | | | FIRE RATED COLUMN ON THE DOOR SCHEDULE. | | | 4.) FBC B 107.2.1, PROVIDE PRODUCT APPROVALS FOR ALL | | | PROPOSED DOORS. | | | 5.) FBC B 107.2.1, PLEASE CORRECT PLAN SHEETS LS 101 & | | | G 000 TO SHOW THE SAME CONSTRUCTION TYPE AS PLAN SHEET | | | LS 101 INDICATES TYPE IIA & G 000 INDICATES TYPE IIB. |
|