Plan Review Notes
Plan Review Notes For Permit 22021416
Permit Number 22021416
Review Stop P
Sequence Number 1
Notes
Date Text
2022-05-03 12:13:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22021416 222 LAKEVIEW AVE FL 10
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6, REVISE PLAN SHEET G001 AND PROVIDE
 PLAN AND ELEVATION DETAILS FOR THE UPGRADED TOILET
 ROOMS INDICATING THE FOLLOWING:
 ***A) CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER
 CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED
 WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL
 PER FBC ACC 604.3.1 AND 604.8.1.1.
 ***B) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 ***C) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 ***D) PER FBC ACC 604.8, TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS.
 ***E) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
 ***F) URINAL: SEE PLAN SHEET IN501/MEN?S RR ELEVATIONS
 AND P-201/PLBG FIXTURE SCHEDULE. IN501 SHOWS URINAL LIP
 AT 24-1/2 INCHES AFF; P-201 INDICATES THE URINAL WILL
 BE ACCESSIBLE WALL-HUNG TYPE WITH THE RIM 17 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR. PER WPB FBC 107.2.,
 CLARIFY AND RECONCILE THE TWO PLANS. PER FBC ACC
 213.3.3, AS THERE IS ONLY ONE URINAL, IT IS NOT
 REQUIRED TO BE ACCESSIBLE. IF THE URINAL IS TO BE
 ACCESSIBLE, PROVIDE CORRECT ELEVATION AND CLEAR FLOOR
 SPACE SHOWING COMPLIANCE WITH FBC ACC 305 AND 605.2.
 ***G) LAVATORIES: A CLEAR FLOOR SPACE COMPLYING WITH
 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE AND
 TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED PER
 FBC ACC 606.2
 ***H) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
 TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT DIMENSION IS
 TO THE REFLECTING SURFACE OF THE MIRROR.
 ***I) SHOW TURNING SPACE FOR COMPLYING WITH FBC ACC
 304.3.1 OR 304.3.2.
 ***J) DRINKING FOUNTAIN: PROVIDE ELEVATION AND CLEAR
 FLOOR SPACE SHOWING COMPLIANCE WITH FBC ACC 305, 306,
 307 AND 602.
 ***K) DRINKING FOUNTAIN: FBC ACC 307.2; PROTRUDING
 OBJECTS AND PROTRUSION LIMITS. OBJECTS WITH LEADING
 EDGES MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES
 ABOVE THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES
 HORIZONTALLY INTO THE CIRCULATION PATH.
  
 2.P-201/FIXTURE SCHEDULE: ELKAY LNTE8K DRINKING
 FOUNTAIN IS DISCONTINUED. PER WPB FBC 107.2.1, SPECIFY
 A DRINKING FOUNTAIN THAT IS CURRENTLY MANUFACTURED AND
 AVAILABLE.
  
 3.P-201/TYP. LAV/SK INSTALLATION; COLD AND/OR HOT WATER
 AS INDICATED ON PLAN. PLANS SHOW COLD WATER RISER. PER
 WPB FBC 107.2.1, PROVIDE SPECIFIC GUIDANCE ON THE PLAN.
 COLD WATER ONLY IS ACCEPTABLE. TEMPERED WATER IS
 ACCEPTABLE. IF TEMPERED WATER IS TO BE PROVIDED,
 SPECIFY HOT WATER SOURCE (AND PROVIDE SPECIFICATION AND
 DETAIL) AND AN APPROVED WATER-TEMPERATURE LIMITING
 DEVICE THAT CONFORMS TO ASSE 1070 OR CSA B125.3.
  
 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUALS FOR THE NEW PLUMBING
 FIXTURES. THEY SHALL BE ON SITE PRIOR TO INSPECTION AND
 MAY BE LISTED ON THE PLANS AS DEFERRED SUBMITTALS IN
 ACCORDANCE WITH WPB FBC 107.3.4.1. DOCUMENT SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION. PROCEED AT YOUR OWN RISK.
  
 5. PLEASE SEE COMMENT 1/***G) URINAL: SEE PLAN SHEET
 IN501/MEN'S RR ELEVATIONS AND P-201/PLBG FIXTURE
 SCHEDULE. IN501 SHOWS URINAL LIP AT 24-1/2 INCHES AFF;
 P-201 INDICATES THE URINAL WILL BE ACCESSIBLE WALL-HUNG
 TYPE WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR. PER WPB FBC 107.2., CLARIFY AND RECONCILE THE
 TWO PLANS. PER FBC ACC 213.3.3, AS THERE IS ONLY ONE
 URINAL, IT IS NOT REQUIRED TO BE ACCESSIBLE. IF THE
 URINAL IS TO BE ACCESSIBLE, PROVIDE CORRECT ELEVATION
 AND CLEAR FLOOR SPACE SHOWING COMPLIANCE WITH FBC ACC
 305 AND 605.2.
  
 6.ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 7. IT IS RECOGNIZED THAT CONDITIONS IN THE WALLS WILL
 NOT BE CLEAR UNTIL THE AFFECTED WALLS ARE OPEN. PER WPB
 FBC 110.2.1, A PLUMBING PRE-INSPECTION WILL BE REQUIRED
 ONCE THE WALLS ARE OPEN AND A REVISED PLAN, SUBMITTED
 AND APPROVED, SHOWING NOTABLE CHANGES TO DESIGN AND
 ROUTING MAY BE REQUIRED BY THE PLUMBING INSPECTOR IN
 COMPLIANCE WITH WPB FBC 107.4 PRIOR TO FINAL
 INSPECTION.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved