Plan Review Notes
Plan Review Notes For Permit 22021413
Permit Number 22021413
Review Stop B
Sequence Number 2
Notes
Date Text
2022-06-28 15:24:13WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22021413
 ADD: 4650 GEORGIA AVE.
 CONT: PERK CONSTRUCTION
 TEL: 561-401-5984
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 28TH/ 2022
 ACTION: DENIED
  
 1) SHEET G1.0 PROJECT DATA & INDEX:
 1A) NOTED: WIND LOAD DESIGN, THE DESIGNER OF RECORD HAS
 PLACED THIS BUILDING IN AN EXPOSURE D.
  
 1B) 2ND REQUEST. THE RISK CATEGORY ASSIGNED TO THIS
 PROJECT IS RISK CATEGORY I. RISK CATEGORY I IS
 BUILDINGS OF AGRICULTURE FACILITIES, MINOR STORAGE
 BUILDINGS, SCREEN ENCLOSURES. PLEASE SEE TABLE 1604.5
 OF THE 2020 FBC-BUILDING CODE THE RISK CATEGORY SHOULD
 READ AS RISK CATEGORY II. RESPONSE SHEET STATES RISK
 CATEGORY HAS BEEN STATED ON THE LIFE SAFETY SHEET,
 ILLEGIBLE HAZY, ALSO ON SHEETG1.0 AS RISK CATEGORY I.
  
 1C) 2ND REQUEST. FUZZY CAN NOT READ WHEN ENLARGED. TYPE
 OF CONSTRUCTION/ OCCUPANCY TYPE IS GIVEN AS B/ FACTORY.
 PLEASE INDICATE WHETHER THE FACTORY OCCUPANCY IS A F1
 OR F2. 2020 FBC-BUILDING CODE SECTIONS 306.2 GROUP F-1
 OR GROUP F-2.
  
 1D) THE QUESTION IS IN THE PROCESS OF AQUAMATION/
 ALKALINE HYDROLYSIS HOW MUCH OF THE CHEMICAL ALKALINE
 WILL BE STORED ON SITE, WILL THE CHEMICAL BE STORED IN
 SOLID FORM POUNDS IN CUBIC FEET, LIQUID GALLONS IN WHAT
 TYPE OF STORAGE, WILL IT BE USED IN A CLOSED SYSTEM OR
 OPEN SYSTEM, PLEASE PROVIDE MSDS SHEETS FOR THIS
 CHEMICAL. ADDITIONAL INFORMATION IS REQUIRED, TABLE
 307.1(1) OF THE 2020 FBC-BUILDING CODE.
  
 1E) 2ND REQUEST. THE RESPONSE NOT SHOWN ON THE PLANS
 FOR COMPLIANCE. TYPE OF CONSTRUCTION/ LEVEL OF
 ALTERATION IS LEFT BLANK, ADDING TO AN EXISTING
 MEZZANINE WOULD BE A ADDITION OF SQUARE FOOTAGE TO THE
 BUILDING AND NEED TO SHOW COMPLIANCE WITH THE 2020
 FBC-EXISTING BUILDING CODE CHAPTER 11 ADDITIONS,
 SECTION 1103.3.1. VERTICAL ADDITIONS.
  
 1F)2ND REQUEST. WITH ADDITIONAL SQUARE FOOTAGE ON THE
 MEZZANINE LEVEL(NEW 2ND FLOOR) THE PROJECT DATA HAS NOT
 DECLARED THE LIVE LOADS FOR STORAGE SEE TABLE 1607.1 OF
 THE 2020 FBC-BUILDING, INDICATE ON THE FLOOR PLANS.
  
 2) THE LIFE SAFETY SHEET LSP:
 2A) MEZZANINES NEED TO SHOW COMPLIANCE WITH SECTION
 505.2.1 THAT THE MEZZANINE CAN NOT BE GRATER THAN 1/3RD
 THE ROOM IT IS IN, THE INSIDE BUILDING LINE FLOOR AREA
 THAT COMMUNICATES WITH THE MEZZANINE IS
 38.32 X 29= 1,111.25 AND THE AREA 5X9.25= 46.25 OR A
 TOTAL OF 1,157.50 SQ. FT. ONE THIRD OF THIS AREA IS
 381.975 SQ. FT. THE AREA SHOWN OF THE PROPOSED
 MEZZANINE IS 573 SQ. FT. OR 191.00 FEET OVER THE
 ALLOWABLE SIZE OF THE MEZZANINE.
  
 2B) COMPLIED. 2ND FLOOR LEVEL.
  
 2C) SEMI-COMPLIED. THE PROPOSED 2ND FLOOR DOES NOT HAVE
 A DOOR AT THE TOP OF THE STAIR ENCLOSE NOR DOES THE
 VERTICAL LIFT.
 1ST ROUND COMMENT. PLEASE SHOW ON THE LIFE SAFETY PLAN
 COMPLIANCE WITH 505.2.2 MEANS OF EGRESS FOR MEZZANINE
 AND CHAPTER 10 OF THE 2020 FBC-BUILDING CODE AND
 SECTION 1019.3 EXCEPTION 1 IF THE MEZZANINE
 REQUIREMENTS CAN NOT BE MET. PROVIDE THE COMMON PATH OF
 TRAVEL FROM THE FURTHEST POINT IN ACCORDANCE WITH TABLE
 1006.2.1. 2020FBC-BUILDING CODE.
  
 3) COMPLIED.
 4A) 2ND REQUEST. SHEET A1.5 SHOWS NEW SINGLE AND PAIR
 OF EXTERIOR SWING DOORS. PLEASE SUBMIT THE COMPONENTS
 AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS
  
 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
 4C) PLEASE NOTE ONCE TO THE TECHNICAL SHEETS SOME WOULD
 OPEN AND SOME WOULD NOT, NOT ABLE TO REVIEW.
  
 5) BUILDING PROVISO: SHEET S-2 SHOWS JOBSITE WELDING.
 WELDED OR BOLTED CONNECTIONS. THIS BUILDING CONTAINS
 EITHER BOLTED AND OR WELDED CONNECTIONS. THE CONTRACTOR
 IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE ACTING CHIEF BUILDING INSPECTOR
 RICHARD BRUNELLE AT 561-805-6670.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED. THE BEST WAY TO COMMUNICATE IS
 BY E-MAIL.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT