Plan Review Notes
Plan Review Notes For Permit 22021413
Permit Number 22021413
Review Stop P
Sequence Number 1
Notes
Date Text
2022-03-08 16:11:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC MC = FLORIDA MECHANICAL CODE 2020 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22021413 4650 GEORGIA AVE
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.A1.4/DETAIL 1: PER FBC ACC 804.3.1, THE CLEAR FLOOR
 OR GROUND SPACE SHALL BE CENTERED ON THE KITCHEN WORK
 SURFACE AND SHALL PROVIDE KNEE AND TOE CLEARANCE
 COMPLYING WITH 306. PER WPB FBC 107.2.1, PROVIDE
 FORWARD APPROACH TO KITCHEN SINK WITH KNEE AND TOE
 CLEARANCE.
  
 2.A1.4/DETAIL 1: PER FBC ACC 804.6.1, PROVIDE A CLEAR
 FLOOR SPACE FOR THE MICROWAVE OVEN.
  
 3. A1.4/DETAIL 1: PER FBC ACC 214.2 AND 214.3, WASHER
 AND DRYER SHALL COMPLY WITH FBC ACC 611; PER WPB FBC
 107.2.1, PROVIDE THE FOLLOWING:
 ***A) A FRONTAL VIEW OF EACH ITEM SHOWING COMPLIANCE
 WITH FBC ACC 611.4.
 ***B) A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH FBC
 ACC 305 POSITIONED FOR PARALLEL APPROACH; THE CLEAR
 FLOOR OR GROUND SPACE SHALL BE CENTERED ON THE
 APPLIANCE.
  
 4.A1.3: PER WPB FBC 107.2.1, FOR CLARIFICATION PLEASE
 PROVIDE THE ADDITIONAL FOLLOWING INFORMATION
 ***A) THE SIDE WALL GRAB BAR FOR THE WATER CLOSET SHALL
 BE 42 INCHES LONG MINIMUM, LOCATED 12 INCHES (305 MM)
 MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 MINIMUM FROM THE REAR WALL PER FBC ACC 604.5.1
 ***B) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 ***C) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 ***D) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4
 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN
 FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 THE DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 ***E) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE
 SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED
 POSITION PER FBC ACC 604.4.
 ***F) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
  
 5.PDFS FOR PLUMBING PLANS HAVE STICKY NOTES ALL OVER,
 MAKING PLANS HARD TO READ. PER WPB FBC 107.2.1, PLEASE
 HIDE OR REMOVE STICKY NOTES ON FUTURE SUBMITTALS.
  
 6.P2.0/DETAIL 8: PER WPB FBC 107.2.1, SHOW TRAP SEAL
 PROTECTION FOR THE FLOOR DRAIN AS REQUIRED BY FBC PL
 1002.4.1.
  
 7. P2.0/DETAIL 7: BOTTLE TRAPS ARE PROHIBITED PER FBC
 PL 1002.2 AND 1002.2(4). PER WPB FBC 107.2.1, REPLACE
 THE TEXT ?BOTTLE TRAP? WITH ?P-TRAP?.
  
 8.P0.0/PLUMBING MATERIAL AND EQUIPMENT NOTE 6: PER WPB
 FBC 107.2.1, PROVIDE A DETAIL FOR INSTALLATION OF THE
 SIOUX CHIEF 695 TRAP PRIMER VALVE FROM WATER
 DISTRIBUTION TO FLOOR DRAIN CONNECTION.
  
 9. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 9. P2.0/DETAIL 4: PER WPB FBC 107.2.1, PROVIDE NOTE AT
 THE PIPE HANGER DETAIL STATING, "HORIZONTAL PIPE SHALL
 BE SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 10.PER WPB FBC 107.2.1, PROVIDE A SCHEMATIC DETAIL FOR
 THE RECIRCULATING PUMP AND PIPING WITH VALVES AND
 CONTROLS; BE SURE TO SHOW CHECK VALVE WITH FULL OPEN
 VALVE IN COLD WATER LINE TO THE WATER HEATERS AHEAD OF
 THE HOT WATER RETURN LINE CONNECTION TO THE COLD WATER
 (SEE FBC PL 604.2).
  
 11.A1.3 AND P3.0: PLUMBING FIXTURE SCHEDULES HAVE
 CONFLICTING, INACCURATE AND MISSING INFORMATION; PER
 WPB FBC 107.2.1, RECONCILE AND CLARIFY THE FOLLOWING:
 ***A) ALL FIXTURES TO HAVE THE SAME MANUFACTURER/MODEL
 NUMBER/DESCRIPTION.
 ***B) WATER HEATER ON A1.3 SCHEDULE IS ELECTRIC AND A
 STORAGE TANK TYPE. P3.0 PROVIDES A SCHEDULE FOR GAS
 FIRED TANKLESS WATER HEATERS. PIPING AND GAS PLANS ALL
 INDICATE THE GAS FIRED TANKLESS WATER HEATERS.
 ***C) RECIRC PUMP MODEL NUMBERS DON'T MATCH
 ***D) DRINKING FOUNTAIN MODEL NUMBERS DON'T MATCH
 ***E) SINKS DON'T MATCH
 ***F) LAVATORIES DON'T MATCH. BE SURE TO INCLUDE THE
 POINT OF USE MIXING VALVE IN BOTH SCHEDULES
 ***G) PROVIDE SPECIFICATION FOR FD-1
 ***H) RECONCILE FIXTURE ID/TAG NUMBERS
 ***I) P3.0 SCHEDULE MISSING THE MOP SINK
 ***J) A1.3 MISSING EMERGENCY SHOWERS EEWS-1 AND ES-1.
  
 12.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE WATER
 HEATER(S)
  
 13. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUALS AND DETAIL(S) FOR
 EEWS-1 AND ES-1.
  
 14.P1.0/ELEVATOR DRAIN:
 ***A) PLEASE NOTE, PER FBC 3002.9, FLOOR DRAINS, SUMPS
 AND SUMP PUMPS SHALL BE PERMITTED AT THE BASE OF THE
 HOISTWAY ENCLOSURE PROVIDED THEY ARE INDIRECTLY
 CONNECTED TO THE PLUMBING SYSTEM. PER WPB FBC 107.2.1,
 PROVIDE COMPLIANT DRAINAGE WITH DETAILS SHOWING
 INDIRECT CONNECTION.
 ***B) PLEASE NOTE PER FBC PL 1003.4.2.1, OIL SEPARATORS
 SHALL HAVE A DEPTH OF NOT LESS THAN 2 FEET BELOW THE
 INVERT OF THE DISCHARGE DRAIN. THE OUTLET OPENING OF
 THE SEPARATOR SHALL HAVE NOT LESS THAN AN 18-INCH WATER
 SEAL. PER WPB FBC 107.2.1, SELECT THE SIZE THAT
 COMPLIES. SIZE EFFLUENT DRAIN IN ACCORDANCE WITH
 MANUFACTURER'S RECOMMENDATIONS PER FBC PL 301.7.
  
 15.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL
 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING
 LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF
 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE
 A MINIMUM SLOPE OF 1/8 INCH PER FOOT".
  
 16. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR CLOTHES
 WASHER PLUMBING CONNECTIONS.
  
 17. P3.0/SANITARY RISER: PER WPB FBC 107.2.1, IDENTIFY
 KS-1 AND W/D.
  
 18. REGARDING THE HORIZONTAL COMBINATION WASTE AND VENT
 SYSTEM:
 ***A) THE DRY 3 INCH VENT FOR THE SYSTEM SHALL CONNECT
 ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE AND
 RISE VERTICALLY TO A POINT NOT LESS THAN 6 INCHES ABOVE
 THE FLOOD LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED
 FIXTURE BEING VENTED PER FBC PL 905.3 AND 905.4.
 ***B) PER WPB FBC 107.2.1, SIZE HORIZONTAL BRANCHES
 CONNECTING THE TD FIXTURE DRAINS.
 ***C) PER WPB FBC 107.2.1, REFER TO FBC PL TABLE 709.1,
 FOOTNOTE (H), TABLE 709.2 AND SECTION 709.4. PROVIDE
 FIXTURE UNIT VALUES FOR FLOOR DRAINS AND TRENCH DRAINS
 AND NOTE TOTAL FIXTURE UNIT COUNT FOR THE SYSTEM.
 CONFIRM THAT THE SIZING OF THE SYSTEM IS IN ACCORDANCE
 WITH FBC PL TABLE 915.2.2. IF NECESSARY, SPLIT THE
 SYSTEM AND ADD A VENT ON THE TRENCH DRAIN SIDE. VENT
 SHALL COMPLY WITH FBC PL 905.3 AND 905.4.
 ***D) PER FBC PL 1002.1, PROVIDE A TRAP FOR EACH TRENCH
 DRAIN
 ***E) PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE TRENCH
 DRAIN.; CONFIRM THAT 3 INCH CONNECTION IS IN ACCORDANCE
 WITH THE MANUFACTURER'S SPECIFICATION/INSTALLATION
 MANUAL. SEE FBC PL 301.7 WHICH STATES IN INSTANCES
 WHERE CONFLICTS OCCUR BETWEEN THIS CODE AND THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS, THE MORE
 RESTRICTIVE PROVISIONS SHALL APPLY.
  
 19. PER FBC PL 604.1, THE DESIGN OF THE WATER
 DISTRIBUTION SYSTEM SHALL CONFORM TO ACCEPTED
 ENGINEERING PRACTICE. METHODS UTILIZED TO DETERMINE
 PIPE SIZES SHALL BE APPROVED. PER WPB FBC 107.2.1 AND
 107.3.5.1.3, PROVIDE CALCULATIONS FOR SIZING OF WATER
 DISTRIBUTION. FBC PL APPENDIX E, SIZING OF WATER PIPING
 SYSTEM IS AN APPROVED METHOD.
  
 20. PER FBC PL 604.9, PROVIDE WATER HAMMER ARRESTORS AT
 THE CLOTHES WASHER. PROVIDE NOTE "WATER-HAMMER
 ARRESTORS SHALL CONFORM TO ASSE 1010"
  
 21. P1.0 SANITARY INDICATES FS-1( FLOOR SINK?) WITH
 WHAT APPEARS TO BE AN INDIRECT WASTE CONNECTION; P3.0
 INDICATES FD-1( FLOOR DRAIN?). PER WPB FBC 107.2.1,
 CLARIFY AND RECONCILE.
 21. PLANS INDICATE EQUIPMENT WITH WATER AND WASTE
 CONNECTIONS. PER WPB FBC 107.2.1, PROVIDE THE
 FOLLOWING:
 ***A) MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL
 FOR THE EQUIPMENT
 ***B) DETAIL(S) SHOWING PLUMBING CONNECTIONS INCLUSIVE
 OF WATER, WASTE AND VENTS.
 ***C) IF PROVISION FOR BACKFLOW PREVENTION IS REQUIRED
 FOR THE WATER CONNECTIONS, IT IS ADVISABLE THAT SUCH
 PROTECTION IS SPECIFIED IN ACCORDANCE WITH FBC PL
 SECTION 608.
  
 22.P2.0/DETAIL 5 IS NOT APPLICABLE. PER WPB FBC
 107.2.1, PROVIDE INDIRECT WASTE CONNECTION FOR
 APPLICABLE CIRCUMSTANCES SHOWING COMPLIANCE WITH FBC PL
 SECTION 802.
  
 23.P1.0/NOTE 3: PER WPB FBC 107.2.1, PROVIDE A DETAIL
 FOR 2 INCH VENT PENETRATION AND RISER AT EXTERIOR.
 PROVIDE DISTANCES FROM ANY INTAKE VENTILATION SHOWING
 COMPLIANCE WITH FBC PL 903.5 AND FBC MC 401.4.
  
 24.P3.0/WATER RISER: AT THE POINT OF ENTRANCE FOR THE
 WATER DISTRIBUTION PROVIDE THE FOLLOWING:
 ***A) PER FBC PL 606.1(2), PROVIDE A FULL OPEN VALVE ON
 THE WATER DISTRIBUTION SUPPLY PIPE AT THE ENTRANCE INTO
 THE STRUCTURE.
 ***B) PER FBC PL 606.2(2), PROVIDE A SHUT-OFF VALVE FOR
 THE HOSE BIBB.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 22021413 4650 GEORGIA AVE
  
  