Plan Review Notes
Plan Review Notes For Permit 22021413
Permit Number 22021413
Review Stop G
Sequence Number 1
Notes
Date Text
2022-03-10 12:22:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC MC = FLORIDA MECHANICAL CODE 2020 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22021413 4650 GEORGIA AVE
  
 1ST REVIEW
  
 GAS COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH FBC FG 402.2 AND
 301.3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER FBC FG
 305.1.
  
 2. DETAIL SHOWS ONE MP REGULATOR FOR THE TWO WATER
 HEATERS. RISER DIAGRAM SHOWS TWO SEPARATE RISERS OUT OF
 THE GROUND TO THE WATER HEATERS WHICH WOULD INDICATE A
 DEDICATED REGULATOR FOR EACH ONE. PER WPB FBC 107.2.1,
 CLARIFY AND RECONCILE THE DRAWINGS.
  
 3. P0.0/GAS FIXTURE LOAD SUMMARY: PER WPB FBC 107.2.1,
 INDICATE QUANTITY OF 2.
  
 4. P0.0: PER WPB FBC 107.2.1, CLEARLY INDICATE MAXIMUM
 DEVELOPED LENGTH OF THE 2LB. SYSTEM PIPING AND THE
 LOW-PRESSURE SYSTEM(S) PIPING.
  
 5. P0.0/NOTE 1: PER WPB FBC 107.2.1, CLARIFY REFERENCE
 ALL ABOVE GROUND PIPING TO BE THE SUPPLY SIDE OF THE MP
 REGULATOR(S)
  
 6. P0.0/NOTE 7: PER WPB FBC 107.2.1, NOTE THE CODE
 REFERENCE AS FLORIDA FUEL GAS CODE 408.2.
  
 7. P0.0: PER WPB FBC 107.2.1, ADD TO GAS NOTES A TABLE
 (SEE FBC FG TABLES 402.4) AND MATERIAL SPECIFICATION
 FOR THE LOW-PRESSURE GAS PIPING; INDICATE INLET
 PRESSURE, PRESSURE DROP AND SPECIFIC GRAVITY. SIZING ON
 P2.0/DETAIL 6 SHALL REFLECT THE REQUIREMENTS OF THE
 TABLE(S).
  
 8. 2.0/DETAIL 6: PER WPB FBC 107.2.1, CLARIFY FUEL
 SOURCE TO INDICATE FROM UTILITY REGULATOR/METER, NOT
 UTILITY.
  
 9. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. COMPLY WITH FBC FG 410.1.
  
 10. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE
 INSTALLATION OF THE MP REGULATOR(S) SHOWING COMPLIANCE
 WITH FBC FG 409.4, 410.2(5)(6)(7).
  
 11. PER WPB FBC 107.2.1, MP REGULATOR VALVE(S) AND
 APPLIANCE VALVE(S) SHOWING COMPLIANCE WITH FBC FG 409.4
 AND 409.5.
  
 12. P3.0/GAS RISER DIAGRAM: PER WPB FBC 107.2.1, PLEASE
 NOTE ON THE PLANS THAT THE SUPPLY SIDE OF THE METER IS
 BY THE UTILITIES.
  
 13. P3.0/GAS RISER DIAGRAM: IT APPEARS THAT THE SUPPLY
 SIDE IN YOUR CALCULATIONS FOR DEVELOPED LENGTH IS
 INCLUDED. PER WPB FBC 107.2.1, PLEASE CLARIFY.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 22021413 4650 GEORGIA AVE
  