| 2022-03-10 12:22:22 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC MC = FLORIDA MECHANICAL CODE 2020 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22021413 4650 GEORGIA AVE |
| | |
| | 1ST REVIEW |
| | |
| | GAS COMMENTS: DENIED |
| | |
| | 1. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER'S |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH FBC FG 402.2 AND |
| | 301.3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER FBC FG |
| | 305.1. |
| | |
| | 2. DETAIL SHOWS ONE MP REGULATOR FOR THE TWO WATER |
| | HEATERS. RISER DIAGRAM SHOWS TWO SEPARATE RISERS OUT OF |
| | THE GROUND TO THE WATER HEATERS WHICH WOULD INDICATE A |
| | DEDICATED REGULATOR FOR EACH ONE. PER WPB FBC 107.2.1, |
| | CLARIFY AND RECONCILE THE DRAWINGS. |
| | |
| | 3. P0.0/GAS FIXTURE LOAD SUMMARY: PER WPB FBC 107.2.1, |
| | INDICATE QUANTITY OF 2. |
| | |
| | 4. P0.0: PER WPB FBC 107.2.1, CLEARLY INDICATE MAXIMUM |
| | DEVELOPED LENGTH OF THE 2LB. SYSTEM PIPING AND THE |
| | LOW-PRESSURE SYSTEM(S) PIPING. |
| | |
| | 5. P0.0/NOTE 1: PER WPB FBC 107.2.1, CLARIFY REFERENCE |
| | ALL ABOVE GROUND PIPING TO BE THE SUPPLY SIDE OF THE MP |
| | REGULATOR(S) |
| | |
| | 6. P0.0/NOTE 7: PER WPB FBC 107.2.1, NOTE THE CODE |
| | REFERENCE AS FLORIDA FUEL GAS CODE 408.2. |
| | |
| | 7. P0.0: PER WPB FBC 107.2.1, ADD TO GAS NOTES A TABLE |
| | (SEE FBC FG TABLES 402.4) AND MATERIAL SPECIFICATION |
| | FOR THE LOW-PRESSURE GAS PIPING; INDICATE INLET |
| | PRESSURE, PRESSURE DROP AND SPECIFIC GRAVITY. SIZING ON |
| | P2.0/DETAIL 6 SHALL REFLECT THE REQUIREMENTS OF THE |
| | TABLE(S). |
| | |
| | 8. 2.0/DETAIL 6: PER WPB FBC 107.2.1, CLARIFY FUEL |
| | SOURCE TO INDICATE FROM UTILITY REGULATOR/METER, NOT |
| | UTILITY. |
| | |
| | 9. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. COMPLY WITH FBC FG 410.1. |
| | |
| | 10. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE |
| | INSTALLATION OF THE MP REGULATOR(S) SHOWING COMPLIANCE |
| | WITH FBC FG 409.4, 410.2(5)(6)(7). |
| | |
| | 11. PER WPB FBC 107.2.1, MP REGULATOR VALVE(S) AND |
| | APPLIANCE VALVE(S) SHOWING COMPLIANCE WITH FBC FG 409.4 |
| | AND 409.5. |
| | |
| | 12. P3.0/GAS RISER DIAGRAM: PER WPB FBC 107.2.1, PLEASE |
| | NOTE ON THE PLANS THAT THE SUPPLY SIDE OF THE METER IS |
| | BY THE UTILITIES. |
| | |
| | 13. P3.0/GAS RISER DIAGRAM: IT APPEARS THAT THE SUPPLY |
| | SIDE IN YOUR CALCULATIONS FOR DEVELOPED LENGTH IS |
| | INCLUDED. PER WPB FBC 107.2.1, PLEASE CLARIFY. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |