Plan Review Notes
Plan Review Notes For Permit 22021413
Permit Number 22021413
Review Stop E
Sequence Number 1
Notes
Date Text
2022-03-21 22:45:42ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM IS NOT CLEAR AND CONCISE. THERE ARE
 MULTIPLE MAINS AFTER THE CT METER. PLEASE PROVIDE CLEAR
 RISER DIAGRAM SHOWING SERVICE DISCONECTING MEANS. THERE
 IS A 800AMP 3-POLE DISCONNECT SHOWN THEN A 700AMP
 3-POLE DISCONNECT DOWNSTREAM. FBC 107.2.1
  
 2. THERE IS AN EQUIPMENT GROUNDING CONDUCTOR SHOWN FROM
 CT METER ENCLOSURE TO SERVICE DISCONNECTING MEANS. THIS
 IS NOT PERMITTED. THE EQUIPMENT GROUNDING CONDUCTOR
 ORIGINATES ON THE LOAD SIDE OF THE SERVICE
 DISCONNECTING MEANS. PLEASE REMOVE ALL EQUIPMENT
 GROUNDING CONDUCTORS ON THE LINE SIDE OF THE SERVICE
 DISCONNECTING MEANS. NEC 250.30
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved