| 2022-03-21 22:45:42 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RISER DIAGRAM IS NOT CLEAR AND CONCISE. THERE ARE |
| | MULTIPLE MAINS AFTER THE CT METER. PLEASE PROVIDE CLEAR |
| | RISER DIAGRAM SHOWING SERVICE DISCONECTING MEANS. THERE |
| | IS A 800AMP 3-POLE DISCONNECT SHOWN THEN A 700AMP |
| | 3-POLE DISCONNECT DOWNSTREAM. FBC 107.2.1 |
| | |
| | 2. THERE IS AN EQUIPMENT GROUNDING CONDUCTOR SHOWN FROM |
| | CT METER ENCLOSURE TO SERVICE DISCONNECTING MEANS. THIS |
| | IS NOT PERMITTED. THE EQUIPMENT GROUNDING CONDUCTOR |
| | ORIGINATES ON THE LOAD SIDE OF THE SERVICE |
| | DISCONNECTING MEANS. PLEASE REMOVE ALL EQUIPMENT |
| | GROUNDING CONDUCTORS ON THE LINE SIDE OF THE SERVICE |
| | DISCONNECTING MEANS. NEC 250.30 |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |