Plan Review Notes
Plan Review Notes For Permit 22021413
Permit Number 22021413
Review Stop B
Sequence Number 1
Notes
Date Text
2022-03-21 17:10:13WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22021413
 ADD: 4650 GEORGIA AVE.
 CONT: PERK CONSTRUCTION
 TEL: 561-401-5984
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY MARCH 21ST/ 2022
 ACTION: DENIED
  
 1) SHEET G1.0 PROJECT DATA & INDEX:
 1A) WIND LOAD DESIGN, THE DESIGNER OF RECORD HAS PLACED
 THIS BUILDING IN AN EXPOSURE D WITH HIGHER EXPOSURE
 PRESSURES. THE DESIGNER OF RECORD CAN DESIGN TO A
 HIGHER STANDARD THAN THE MINIMUM CODE. THE CORRECT WIND
 EXPOSURE IS CONSIDERED A C EXPOSURE.
  
 1B) THE RISK CATEGORY ASSIGNED TO THIS PROJECT IS RISK
 CATEGORY I. RISK CATEGORY I IS BUILDINGS OF AGRICULTURE
 FACILITIES, MINOR STORAGE BUILDINGS, SCREEN ENCLOSURES.
 PLEASE SEE TABLE 1604.5 OF THE 2020 FBC-BUILDING CODE
 THE RISK CATEGORY SHOULD READ AS II.
  
 1C) OCCUPANCY TYPE IS GIVEN AS B/ FACTORY. PLEASE
 INDICATE WHETHER THE FACTORY OCCUPANCY IS A F1 OR F2.
 2020 FBC-BUILDING CODE SECTIONS 306.2 GROUP F-1 OR
 GROUP F-2.
  
 1D) THE QUESTION IS IN THE PROCESS OF AQUAMATION/
 ALKALINE HYDROLYSIS HOW MUCH OF THE CHEMICAL ALKALINE
 WILL BE STORED ON SITE, WILL THE CHEMICAL BE STORED IN
 SOLID FORM POUNDS IN CUBIC FEET, LIQUID GALLONS IN WHAT
 TYPE OF STORAGE, WILL IT BE USED IN A CLOSED SYSTEM OR
 OPEN SYSTEM, PLEASE PROVIDE MSDS SHEETS FOR THIS
 CHEMICAL. ADDITIONAL INFORMATION IS REQUIRED, TABLE
 307.1(1) OF THE 2020 FBC-BUILDING CODE.
  
 1E) LEVEL OF ALTERATION IS LEFT BLANK, ADDING TO AN
 EXISTING MEZZANINE WOULD BE A ADDITION OF SQUARE
 FOOTAGE TO THE BUILDING AND NEED TO SHOW COMPLIANCE
 WITH THE 2020 FBC-EXISTING BUILDING CODE CHAPTER 11
 ADDITIONS, SECTION 1103.3.1. VERTICAL ADDITIONS.
  
 1F) WITH ADDITIONAL SQUARE FOOTAGE ON THE MEZZANINE
 LEVEL THE PROJECT DATA HAS NOT DECLARED THE LIVE LOADS
 FOR STORAGE SEE TABLE 1607.1 OF THE 2020 FBC-BUILDING.
  
 2) THE LIFE SAFETY SHEET LSP:
 2A) MEZZANINES NEED TO SHOW COMPLIANCE WITH SECTION
 505.2.1 THAT THE MEZZANINE CAN NOT BE GRATER THAN 1/3RD
 THE ROOM IT IS IN, THE INSIDE BUILDING LINE FLOOR AREA
 THAT COMMUNICATES WITH THE MEZZANINE IS
 38.32 X 29= 1,111.25 AND THE AREA 5X9.25= 46.25 OR A
 TOTAL OF 1,157.50 SQ. FT. ONE THIRD OF THIS AREA IS
 381.975 SQ. FT. THE AREA SHOWN OF THE PROPOSED
 MEZZANINE IS 573 SQ. FT. OR 191.00 FEET OVER THE
 ALLOWABLE SIZE OF THE MEZZANINE.
  
 2B) THE AREA OF THE MEZZANINE ON THE 2ND LEVEL ALSO HAS
 WALLS MAKING IT WHERE IT DOES NOT COMMUNICATE WITH THE
 1ST FLOOR, 505.2.3 OPENNESS EXCEPTION 3 WILL ALLOW IT
 WHERE THE OCCUPANT LOAD OF THE MEZZANINE ENCLOSED SPACE
 OCCUPANT LOAD IS NOT GREATER THAN 10 PLEASE PROVIDE THE
 BREAK OUT OF THE ENCLOSED MEZZANINE BY ITSELF IN THE
 OCCUPANT LOAD TABLE. THANK YOU.
  
 2C) PLEASE SHOW ON THE LIFE SAFETY PLAN COMPLIANCE WITH
 505.2.2 MEANS OF EGRESS FOR MEZZANINE AND CHAPTER 10 OF
 THE 2020 FBC-BUILDING CODE AND SECTION 1019.3 EXCEPTION
 1 IF THE MEZZANINE REQUIREMENTS CAN NOT BE MET. PROVIDE
 THE COMMON PATH OF TRAVEL FROM THE FURTHEST POINT IN
 ACCORDANCE WITH TABLE 1006.2.1. 2020FBC-BUILDING CODE.
  
 3) SHEET A1.4 THE ENLARGED BREAKROOM THE WASHER DRYER
 DOES NOT SHOW THEIR OPERABLE PARTS IN COMPLIANCE WITH
 THE 2020 FBC-ACCESS. CODE SECTION 611.3 OPERABLE PARTS,
 INCLUDING DOORS, LINT SCREENS, DETERGENT AND BLEACH
 COMPARTMENTS IN COMPLIANCE WITH 309.3 HEIGHT. OPERABLE
 PARTS SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH
 RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
 308 REACH RANGES
 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 4A) SHEET A1.5 SHOWS NEW SINGLE AND PAIR OF EXTERIOR
 SWING DOORS. . PLEASE SUBMIT THE COMPONENTS AND
 CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS
  
 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 5) SHEET S-2 SHOWS JOBSITE WELDING. WELDED OR BOLTED
 CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND
 OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666 OR ACTING CHIEF BUILDING INSPECTOR
 RICHARD BRUNELLE AT 561-805-6670.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  