| Notes |
| Date |
Text |
| 2022-08-24 09:22:07 | INSUFFICIENT | | | | | | 1) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED | | | SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, THE | | | SIDEWALK, EDGE OF PAVEMENT AND ANY TREES WITHIN THE | | | RIGHT-OF-WAY ALONG THE ENTIRE FIBER CONDUIT PATH SO | | | THAT STAFF CAN VERIFY THAT THE BORE AND HANDHOLES ARE | | | WITHIN THE RIGHT-OF-WAY. | | | | | | 2) HANDHOLE 00+00 IS NOTED ON THE ENGINEERING PLAN AS | | | EXISTING; HOWEVER, NO HANDHOLE IS VISIBLE IN THE APRIL | | | 2022 STREETVIEW AT THIS LOCATION. THE SURVEY SHOULD | | | VERIFY THIS CONDITION. | | | | | | 2) THE TUBULAR MARKERS ARE NOT PERMITTED. MARKERS MAY | | | ONLY BE INSTALLED WITHIN THE HANDHOLES OR OTHERWISE | | | BURIED. | | | | | | 3) THE BORE DEPTH IS SUFFICIENT TO AVOID TREE ROOTS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | | | | |
|