| Plan Review Notes For Permit 22021383 |
| Permit Number |
22021383 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2022-12-19 15:52:01 | RESIDENTIAL (R3) SIXTH BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | SUBMITTAL #22021383 | | | 310 DYER RD | | | | | | HURRICANE SHUTTERS: | | | 7(B)REVISE SHUTTERS INSTALLATION SCHEDULE: | | | | | | PREVIOUS COMMENT: | | | (4)NEED TO COMPLETE THE SHUTTERS GLASS SEPARATION | | | COLUMN. SEE PRODUCT APPROVAL FOR REQUIRED SEPARATION. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | GLASS SEPARATION IS INCORRECT FOR WALL MOUNT | | | INSTALLATION. SEE SHEET 2 OF 11 AND REVISE AS REQUIRED. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | PREVIOUS COMMENT: | | | (3)NEED TO COMPLETE THE ANCHOR SPACING COLUMN. SPECIFY | | | ANCHOR SPACING AT TOP AND BOTTOM. | | | SEC. R301.2.1 FBC-RESIDENTIAL. | | | | | | RESPONSE: | | | ANCHOR SPACING IS INCORRECT FOR WALL MOUNT | | | INSTALLATION. SEE SHEET 6 OF 11 AND REVISE AS REQUIRED. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE | | | REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|